Need assistance or guidance?

Contact us @: 1-800-301-9097
Login / Register Contact Us
 
ioLogik E1214 - Remote Ethernet I/O, 6DI/6Relay, 2-port Switch by MOXA

ioLogik E1214 - Remote Ethernet I/O, 6DI/6Relay, 2-port Switch
by MOXA

Write a review Write a review
  • Support Modbus/TCP Protocol
  • Active communication with patented Active OPC Server
  • 2-port Ethernet switch for daisy-chain topologies
  • Easy mass deployment and configuration with ioSearch utility
  • Save time and wiring cost with peer-to-peer communication
  • User-defined Modbus/TCP addressing
  • Simplify I/O managment with MXIO library on either Windows or Linux platform
  • Supports SNMPv1/v2c
  • UL/cUL Class I Division 2, ATEX Zone 2 certification
  • Wide operating temperature: -40 to 75°C ( -40 to 167°F )
  • Mfg SKU # : ioLogik E1214
    Our Price : $265.80
    Stock : 1151
    Quantity :

    Introduction

    Daisy-chained Ethernet I/O Connection

    A new daisy-chained Ethernet I/O concept is now available. The ioLogik E1214 industrial Ethernet remote I/O has two embedded Ethernet switch ports that allow information to flow to another local Ethernet device or connect to the next ioLogik in the daisy-chain.

    Applications such as factory automation, security and surveillance systems, and tunnel monitoring, can make use of daisy-chained Ethernet for building multi-drop I/O networks over standard Ethernet cables. Many industrial automation users are familiar with the multi-drop configuration typically used in fieldbus applications. The daisy-chain function on the Ethernet remote I/O ioLogik E1214 not only increases the connection between machines and panels, but also lowers the cost of buying separate Ethernet switches, and at the same time reduces labor fees and cabling by a large percentage. For example, if a production facility contains 700 stations (20 points per station), the wiring cost reduction can reach 15% of the total implementation cost.

     

     

    Saving Time and Wiring Costs with Peer-to-Peer Communications

    In remote automation applications, the control room and sensors are often far removed, making wiring over long distances a constant challenge. With peer-to-peer networking, users may now map a pair of ioLogik E1200 series modules so that input values will be directly transferred to output channels, greatly simplifying the wiring process and reducing wiring costs.

     

    User-definable Modbus/TCP Addressing for Painless Upgrading of Existing Systems

    For Modbus devices that are controlled and detected by fixed addresses, users need to spend a vast amount of time researching and verifying the configurations. Users need to locate each device’s networking details like I/O channels, or vendor-defined addresses to enable the initial or start address of a SCADA system or PLC. The ioLogik E1200, with user-definable Modbus/TCP addressing, offers greater flexibility, and setup is easy. Instead of worrying about individual devices, users simply configure the function and address map to fit their needs.

    ioLogik E1214 Specifications
     Inputs and Outputs
    Digital Inputs 6 channels
    Relay Outputs 6 channels
    Isolation 3k VDC or 2k Vrms
     Digital Input
    Sensor Type Wet Contact (NPN or PNP), Dry Contact
    I/O Mode DI or Event Counter
    Dry Contact • On: short to GND
    • Off: open
    Wet Contact (DI to COM) • On: 10 to 30 VDC 
    • Off: 0 to 3 VDC
    Common Type 6 points per COM
    Counter Frequency 250 Hz
    Digital Filtering Time Interval Software Configurable
     Relay Output
    Type Form A (N.O.) power relay
    Contact Current Rating Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC
    Breakdown Voltage 500 VAC
    Relay On/Off Time 1500 ms (max.)
    Initial Insulation Resistance 1000 M ohms (min.) @ 500 VDC
    Mechanical Endurance 5,000,000 operations
    Electrical Endurance 100,000 operations @ 5 A resistive load
    Contact Resistance 100 m ohms (max.)
    Pulse Output 0.3 Hz at rated load
    Note Ambient humidity must be non-condensing and remain between 5 and 95%. The relays of the ioLogik E1214 may malfunction when operating in high condensation environments below 0° Celsius.
     Power Requirements
    Power Consumption 188 mA @ 24 VDC
     MTBF (mean time between failures)
    Time 808,744 hrs
    Database Telcordia (Bellcore)
    Common Specifications
     LAN
    Ethernet 2 switched 10/100 Mbps RJ45 ports
    Protection 1.5 kV magnetic isolation
    Protocols Modbus/TCP, TCP/IP, UDP, DHCP, BOOTP, HTTP
     Power Requirements
    Power Input 24 VDC nominal, 12 to 36 VDC
     Physical Characteristics
    Wiring I/O cable max. 14 AWG
    Dimensions 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
    Weight Under 200 g
    Mounting DIN rail or wall
     Environmental Limits
    Operating Temperature Standard Models: -10 to 60°C (14 to 140°F)
    Wide Temp. Models: -40 to 75°C (-40 to 167°F)
    Storage Temperature -40 to 85°C (-40 to 185°F)
    Ambient Relative Humidity 5 to 95% (non-condensing)
    Altitude Up to 2000 m
    Note Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
     Standards and Certifications
    Safety UL 508
    EMI EN 55022; EN 61000-3-2; EN 61000-3-3; 
    FCC Part 15, Subpart B, Class A
    EMS EN 55024, EN 61000-4-2, EN 61000-4-3, 
    EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, 
    EN 61000-4-8, EN 61000-4-11
    Shock IEC 60068-2-27
    Freefall IEC 60068-2-32
    Vibration IEC 60068-2-6
    Green Product RoHS, CRoHS, WEEE
    Hazardous Location UL/cUL Class I Diision 2, ATEX Zone 2