QUINT-PS/ 1AC/24DC/20/CO - 23208988 |
QUINT-PS/ 1AC/24DC/ 5/CO - 23209088 |
QUINT-PS/ 1AC/24DC/10/CO - 23209118 |
Environmental Product Compliance |
REACH SVHC |
Lead 7439-92-1 |
Lead 7439-92-1 |
Lead 7439-92-1 |
China RoHS |
Environmentally Friendly Use Period = 25; |
Environmentally Friendly Use Period = 25; |
Environmentally Friendly Use Period = 25; |
General |
Net weight |
1.7 kg |
0.7 kg |
1.1 kg |
Efficiency |
> 93 % (for 230 V AC and nominal values) |
> 90 % (for 230 V AC and nominal values) |
> 92.5 % (for 230 V AC and nominal values) |
Insulation voltage input/output |
4 kV AC (type test) |
4 kV AC (type test) |
4 kV AC (type test) |
|
2 kV AC (routine test) |
2 kV AC (routine test) |
2 kV AC (routine test) |
Insulation voltage input / PE |
3.5 kV AC (type test) |
3.5 kV AC (type test) |
3.5 kV AC (type test) |
|
2 kV AC (routine test) |
2 kV AC (routine test) |
2 kV AC (routine test) |
Insulation voltage output / PE |
500 V DC (routine test) |
500 V DC (routine test) |
500 V DC (routine test) |
Protection class |
I |
I |
I |
Degree of protection |
IP20 |
IP20 |
IP20 |
MTBF (IEC 61709, SN 29500) |
> 900000 h (25 °C) |
> 1134000 h (25 °C) |
> 940000 h (25 °C) |
|
> 520000 h (40 °C) |
> 635000 h (40 °C) |
> 530000 h (40 °C) |
|
|
|
> 230000 h (60 °C) |
Mounting position |
horizontal DIN rail NS 35, EN 60715 |
horizontal DIN rail NS 35, EN 60715 |
horizontal DIN rail NS 35, EN 60715 |
Assembly instructions |
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Standards and Regulations |
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Conformance with EMC Directive 2014/30/EU |
Conformance with EMC Directive 2014/30/EU |
Noise emission |
EN 55011 (EN 55022) |
EN 55011 (EN 55022) |
EN 55011 (EN 55022) |
Noise immunity |
EN 61000-6-2:2005 |
EN 61000-6-2:2005 |
EN 61000-6-2:2005 |
Connection in acc. with standard |
CSA |
CSA |
CSA |
Standards/regulations |
EN 61000-4-2 |
EN 61000-4-2 |
EN 61000-4-2 |
Contact discharge |
4 kV (Test Level 2) |
4 kV (Test Level 2) |
4 kV (Test Level 2) |
Standards/regulations |
EN 61000-4-3 |
EN 61000-4-3 |
EN 61000-4-3 |
Frequency range |
80 MHz ... 1 GHz |
80 MHz ... 1 GHz |
80 MHz ... 1 GHz |
Test field strength |
10 V/m (Test Level 3) |
10 V/m (Test Level 3) |
10 V/m (Test Level 3) |
Frequency range |
1.4 GHz ... 2 GHz |
1.4 GHz ... 2 GHz |
1.4 GHz ... 2 GHz |
Test field strength |
3 V/m (Test Level 2) |
3 V/m (Test Level 2) |
3 V/m (Test Level 2) |
Standards/regulations |
EN 61000-4-4 |
EN 61000-4-4 |
EN 61000-4-4 |
Comments |
Criterion B |
Criterion B |
Criterion B |
Standards/regulations |
EN 61000-6-3 |
EN 61000-6-3 |
EN 61000-6-3 |
|
EN 61000-4-6 |
EN 61000-4-6 |
EN 61000-4-6 |
Frequency range |
0.15 MHz ... 80 MHz |
0.15 MHz ... 80 MHz |
0.15 MHz ... 80 MHz |
Voltage |
10 V (Test Level 3) |
10 V (Test Level 3) |
10 V (Test Level 3) |
Low Voltage Directive |
Conformance with LV directive 2006/95/EC |
Conformance with LV directive 2006/95/EC |
Conformance with LV directive 2006/95/EC |
Standard - Electrical safety |
IEC 60950-1/VDE 0805 (SELV) |
IEC 60950-1/VDE 0805 (SELV) |
IEC 60950-1/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations |
EN 50178/VDE 0160 (PELV) |
EN 50178/VDE 0160 (PELV) |
EN 50178/VDE 0160 (PELV) |
Standard – Safety extra-low voltage |
IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
Standard - Safe isolation |
DIN VDE 0100-410 |
DIN VDE 0100-410 |
DIN VDE 0100-410 |
Standard – Limitation of mains harmonic currents |
EN 61000-3-2 |
EN 61000-3-2 |
EN 61000-3-2 |
Standard - Equipment safety |
BG (design tested) |
BG (design tested) |
BG (design tested) |
Shipbuilding approval |
DNV GL (EMC B, only with upstream filter) |
DNV GL (EMC A) |
DNV GL (EMC B), ABS, LR, RINA, NK, BV |
UL approvals |
UL/C-UL listed UL 508 |
UL/C-UL listed UL 508 |
UL/C-UL listed UL 508 |
|
UL/C-UL Recognized UL 60950-1 |
UL/C-UL Recognized UL 60950-1 |
UL/C-UL Recognized UL 60950-1 |
|
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
DeviceNet approval |
DeviceNet™ Power Supply Conformance Tested |
DeviceNet™ Power Supply Conformance Tested |
DeviceNet™ Power Supply Conformance Tested |
Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
|
15 Hz ... 150 Hz, 2.3g, 90 min. |
15 Hz ... 150 Hz, 2.3g, 90 min. |
15 Hz ... 150 Hz, 2.3g, 90 min. |
Approval - requirement of the semiconductor industry with regard to mains voltage dips |
SEMI F47-0706 Compliance Certificate |
SEMI F47-0706 Compliance Certificate |
SEMI F47-0706 Compliance Certificate |
Information technology equipment - safety (CB scheme) |
IEC 60950-1 (2nd Edition) |
IEC 60950-1 (2nd Edition) |
IEC 60950-1 (2nd Edition) |
Rail applications |
EN 50121-4 |
EN 50121-4 |
EN 50121-4 |
Noxious gas test |
ISA-S71.04-1985 G3 Harsh Group A |
ISA-S71.04-1985 G3 Harsh Group A |
ISA-S71.04-1985 G3 Harsh Group A |
ATEX |
II 3 G Ex nA nC IIC T4 Gc |
II 3 G Ex nA nC IIC T4 Gc |
II 3 G Ex nA nC IIC T4 Gc |
|
SIQ 14 ATEX 137 X |
TÜV 11 ATEX 555674 X |
TÜV 11 ATEX 079480 X |
IECEx |
Ex nA nC IIC T4 Gc |
Ex nA nC IIC T4 Gc |
Ex nA nC IIC T4 Gc |
|
IECEx SIQ 14.0001X |
IECEx TUN 11.0002X |
IECEx TUN 11.0007X |
Overvoltage category (EN 62477-1) |
III |
III |
III |
Connection data, input |
Connection method |
Screw connection |
Pluggable screw connection |
Pluggable screw connection |
Conductor cross section solid min. |
0.2 mm² |
0.2 mm² |
0.2 mm² |
Conductor cross section solid max. |
6 mm² |
2.5 mm² |
2.5 mm² |
Conductor cross section flexible min. |
0.2 mm² |
0.2 mm² |
0.2 mm² |
Conductor cross section flexible max. |
4 mm² |
2.5 mm² |
2.5 mm² |
Conductor cross section AWG min. |
18 |
20 |
16 |
Conductor cross section AWG max. |
10 |
12 |
12 |
Stripping length |
7 mm |
7 mm |
7 mm |
Screw thread |
M4 |
M3 |
M3 |
Output data |
Nominal output voltage |
24 V DC ±1 % |
24 V DC ±1 % |
24 V DC ±1 % |
Setting range of the output voltage (USet) |
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) |
20 A (-25 °C ... 60 °C, UOUT = 24 V DC) |
5 A (-25 °C ... 60 °C, UOUT = 24 V DC) |
10 A (-25 °C ... 60 °C, UOUT = 24 V DC) |
POWER BOOST (IBoost) |
26 A (-25°C ... 40°C permanent, UOUT = 24 V DC ) |
7.5 A (-25°C ... 40°C permanent, UOUT = 24 V DC ) |
15 A (-25°C ... 40°C permanent, UOUT = 24 V DC ) |
Selective Fuse Breaking (ISFB) |
120 A (12 ms) |
30 A (12 ms) |
60 A (12 ms) |
Derating |
60 °C ... 70 °C (2.5%/K) |
60 °C ... 70 °C (2.5%/K) |
60 °C ... 70 °C (2.5%/K) |
Connection in parallel |
Yes, for redundancy and increased capacity |
Yes, for redundancy and increased capacity |
Yes, for redundancy and increased capacity |
Connection in series |
yes |
yes |
yes |
Feedback resistance |
max. 35 V DC |
max. 35 V DC |
max. 35 V DC |
Protection against surge voltage on the output |
< 32 V DC |
< 32 V DC |
< 32 V DC |
Control deviation |
< 1 % (change in load, static 10 % ... 90 %) |
< 1 % (change in load, static 10 % ... 90 %) |
< 1 % (change in load, static 10 % ... 90 %) |
|
< 2 % (change in load, dynamic 10 % ... 90 %) |
< 2 % (change in load, dynamic 10 % ... 90 %) |
< 2 % (change in load, dynamic 10 % ... 90 %) |
|
< 0.1 % (change in input voltage ±10 %) |
< 0.1 % (change in input voltage ±10 %) |
< 0.1 % (change in input voltage ±10 %) |
Residual ripple |
< 30 mVPP (with nominal values) |
< 40 mVPP (with nominal values) |
< 50 mVPP (with nominal values) |
Output power |
480 W |
120 W |
240 W |
Typical response time |
< 0.6 s |
< 0.15 s |
< 0.15 s |
Maximum power dissipation in no-load condition |
8 W |
3 W |
9.1 W |
Power loss nominal load max. |
40 W |
15 W |
22 W |
Connection data for signaling |
Conductor cross section solid min. |
0.2 mm² |
0.2 mm² |
0.2 mm² |
Conductor cross section solid max. |
6 mm² |
2.5 mm² |
2.5 mm² |
Conductor cross section flexible min. |
0.2 mm² |
0.2 mm² |
0.2 mm² |
Conductor cross section flexible max. |
4 mm² |
2.5 mm² |
2.5 mm² |
Conductor cross section AWG min. |
18 |
20 |
16 |
Conductor cross section AWG max. |
10 |
12 |
12 |
Screw thread |
M4 |
M3 |
M3 |
Dimensions |
Width |
90 mm |
40 mm |
60 mm |
Height |
130 mm |
130 mm |
130 mm |
Depth |
125 mm |
125 mm |
125 mm |
Width with alternative assembly |
122 mm |
122 mm |
122 mm |
Height with alternative assembly |
130 mm |
130 mm |
130 mm |
Depth with alternative assembly |
93 mm |
43 mm |
63 mm |
Weight per piece |
1700.0 GRM |
700.0 GRM |
1100.0 GRM |
Input data |
Nominal input voltage range |
100 V AC ... 240 V AC |
100 V AC ... 240 V AC |
100 V AC ... 240 V AC |
|
110 V DC ... 250 V DC |
110 V DC ... 250 V DC |
110 V DC ... 250 V DC |
Input voltage range |
85 V AC ... 264 V AC |
85 V AC ... 264 V AC |
85 V AC ... 264 V AC |
|
90 V DC ... 410 V DC +5 % (UL 508: ≤ 250 V DC) |
90 V DC ... 410 V DC +5 % (UL 508: ≤ 250 V DC) |
90 V DC ... 410 V DC +5 % (UL 508: ≤ 250 V DC) |
Dielectric strength maximum |
300 V AC |
300 V AC |
300 V AC |
AC frequency range |
45 Hz ... 65 Hz |
45 Hz ... 65 Hz |
45 Hz ... 65 Hz |
Frequency range DC |
0 Hz |
0 Hz |
0 Hz |
Discharge current to PE |
< 3.5 mA |
< 3.5 mA |
< 3.5 mA |
Current consumption |
5.1 A (120 V AC) |
1.2 A (120 V AC) |
2.2 A (120 V AC) |
|
2.3 A (230 V AC) |
0.6 A (230 V AC) |
1.3 A (230 V AC) |
|
4.9 A (110 V DC) |
1.3 A (110 V DC) |
2.5 A (110 V DC) |
|
2.4 A (220 V DC) |
0.6 A (220 V DC) |
1.2 A (220 V DC) |
Nominal power consumption |
569 VA |
141 VA |
303 VA |
Inrush surge current |
< 20 A |
< 15 A |
< 15 A |
Mains buffering |
typ. 32 ms (120 V AC) |
typ. 55 ms (120 V AC) |
typ. 36 ms (120 V AC) |
|
typ. 32 ms (230 V AC) |
typ. 55 ms (230 V AC) |
typ. 36 ms (230 V AC) |
Input fuse |
12 A (slow-blow, internal) |
5 A (slow-blow, internal) |
10 A (slow-blow, internal) |
Choice of suitable circuit breakers |
10 A ... 16 A (AC: Characteristics B, C, D, K) |
6 A ... 16 A (AC: Characteristics B, C, D, K) |
10 A ... 20 A (AC: Characteristics B, C, D, K) |
Type of protection |
Transient surge protection |
Transient surge protection |
Transient surge protection |
Protective circuit/component |
Varistor, gas-filled surge arrester |
Varistor |
Varistor, gas-filled surge arrester |
Connection data, onput |
Connection method |
Screw connection |
Pluggable screw connection |
Pluggable screw connection |
Conductor cross section solid min. |
0.2 mm² |
0.2 mm² |
0.2 mm² |
Conductor cross section solid max. |
6 mm² |
2.5 mm² |
2.5 mm² |
Conductor cross section flexible min. |
0.2 mm² |
0.2 mm² |
0.2 mm² |
Conductor cross section flexible max. |
4 mm² |
2.5 mm² |
2.5 mm² |
Conductor cross section AWG min. |
12 |
20 |
16 |
Conductor cross section AWG max. |
10 |
12 |
12 |
Stripping length |
7 mm |
7 mm |
7 mm |
Screw thread |
M4 |
M3 |
M3 |
Ambient conditions |
Degree of protection |
IP20 |
IP20 |
IP20 |
Ambient temperature (operation) |
-40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
-40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
-40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (storage/transport) |
-40 °C ... 85 °C |
-40 °C ... 85 °C |
-40 °C ... 85 °C |
Max. permissible relative humidity (operation) |
100 % (at 25 °C, non-condensing) |
100 % (at 25 °C, non-condensing) |
100 % (at 25 °C, non-condensing) |
Climatic class |
3K3 (in acc. with EN 60721) |
3K3 (in acc. with EN 60721) |
3K3 (in acc. with EN 60721) |
Degree of pollution |
2 |
2 |
2 |
Installation height |
6000 m |
5000 m |
5000 m |
Approvals |
|
- ABS
- DNV GL
- BV
- RINA
- cUL Recognized
- cUL Listed
- IECEE CB Scheme
- LR
- UL Listed
- IECEE CB Scheme
- cULus Listed
- UL Recognized
- EAC
- cULus Recognized
- NK
- CSA
- Bauartgeprüft
|