IDPS-24-40-XT |
IDPS-48-240-XT |
UNO-PS/1AC/24DC/150W |
TRIO-PS/1AC/48DC/10 |
Output |
Nominal DC Voltage |
24 V |
48 V |
24 V |
48 V |
Max Current |
1.7 A |
5 A |
6.25 A |
10 A |
Rated Power |
40.8 watts |
240 watts |
150 watts |
480 watts |
Ripple and Noise |
150 mV p-p |
< 40 mVpp |
< 50 mVpp |
Adjustable Voltage Range |
24 - 30 V |
48 - 53 V |
24 - 28 V |
30 to 56 V DC |
Load De-rating |
De-rating from 60C
60% of full load at 70C |
De-rating from 40C
0% of full load at 70C |
55 °C ... 70 °C (2.5%/K) |
55 °C ... 70 °C (2.5%/K) |
Output Connectors |
4-pin terminal block ( V+,V-,V+,V- ) |
Input |
Input Voltage Range |
85 - 264VAC
120 - 370VDC |
85 - 264VAC |
Frequency Range |
47 – 63Hz |
45 Hz - 65 Hz |
Efficiency ( Typical ) |
88% |
85% |
>94% |
>91% |
AC Current ( Typical ) |
1.1A/115VAC
0.7A/230VAC |
2.8A/115VAC
1.4A/230VAC |
1.4 A/120 VAC
0.8 A/230 VA |
4.6 A/120 VAC
2.4 A/230 VAC |
Inrush Current ( Typical ) |
30A/115VAC
60A/230VAC |
27A/115VAC
45A/230VAC |
< 50A ( typical ) |
< 15A |
Input Connectors |
3-pin terminal block |
2-pin terminal block |
3-pin terminal block |
Protection |
Over Voltage |
31.2 - 36V |
54 – 60V |
- |
limited to approx. 60 V DC |
Environmental Specifications |
Operating Temperature Ranges |
-20 to 70C
( -4 to 158F ) |
-10 to 70C
( 14 to 158F ) |
-25 °C to 70 °C
(-13 to 158F ) |
Storage Temperature Range |
-40 to 85C
( -40 to 185F ) |
-20 to 85C
( -4 to 185F ) |
-40 to 85C
( -40 to 185F ) |
Operating Humidity Range |
20 - 90% RH non-condensing |
≤ 95 % (at 25 °C, non-condensing) |
95 % (at 25 °C, non-condensing) |
Din Rail Mountable |
Mounts to standard 35 mm DIN rail in accordance with DIN EN 60175 |
Mounts to standard 35 mm DIN rail in accordance with DIN EN 60175 |
MTBF |
301,700 hours
based on MIL-HDBK-217F @ 25C |
289,900 hours
based on MIL-HDBK-217F @ 25C |
> 868000 h (40°C)
(IEC 61709, SN 29500) |
> 500 000 h in acc. with IEC 61709 (SN 29500) |
Product Weight and Dimensions |
Weight |
0.26kg
0.57lbs |
1.12kg
2.5lbs |
0.5 kg
1.1lbs |
1.9 kg
4.2lbs |
Dimensions |
40 x 90 x 100mm,
1.57 x 3.54 x 3.94 inches |
125.5 x 125.2 x 100mm
4.94 x 4.93 x 3.94 inches |
37 x 130 x 125mm |
115 x 130 x 152.5mm |
Packaging |
Shipping Weight |
0.29kg
0.64lbs |
1.23kg
2.7lbs |
0.6 Kg
1.3lbs |
2.09 Kg
4.6lbs |
Shipping Dimensions |
45 x 105 x 110mm
1.8 x 4.1, 4.3 inches |
145 x 145 x 125mm
5.7 x 5.7x 4.9 inches |
200 x 300 x 70 mm
7.9 x 11.8 x 2.8 inches |
200 x 230 x 150 mm
7.9 x 9.0 x 5.9 inches |
Standards and Certifications |
Safety |
UL508, UL60950-1, TUV EN60950-1 |
EN 60950-1/VDE 0805 (SELV) |
EN 60950-1/VDE 0805 (SELV) |
Emissions |
EN55011, EN55022 (CISPR22) |
EN55011, EN55022 (CISPR22) |
EN61204-3 , Class B EN61000-3-2,-3 |
EN61204-3 , Class B EN61000-3-2,-3 |
Mechanical Stability |
Vibration: IEC 60068-2-6 |
Vibration: IEC 60068-2-6 |
EMC and Immunity |
EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A |
EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A |
Conformance with EMC Directive 2014/30/EU EN 61000-6-2:2005 |
Industrial Safety |
UL508 (Safety standard for Industrial Control Equipment ) |
Class I, Div. 2 Group A, B, C, D HazardousLocations T4 approved |
- |
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
- |
Rail applications |
- |
- |
- |
EN 50121-4 |
Environmental |
Reach, RoHS and WEEE Compliant |
Reach and RoHS Compliant |
Other |
EAR99 |
EAR99 |
HTSUS Number: 8517.62.0050 |
HSTUS Number: 8504.40.30 |