Ambient Conditions |
Ambient temperature (operation) |
-40 °C ... 70 °C |
Ambient temperature (storage/transport) |
-40 °C ... 70 °C |
Degree of protection |
IP20 |
Protective circuit |
IEC test classification |
B2 |
C1 |
C2 |
C3 |
D1 |
Maximum continuous voltage UC |
≤ 3.3 V DC (± 60 V DC/PoE+) |
Rated current |
≤ 1.5 A (25 °C) |
Operating effective current IC at UC |
≤ 1 µA |
Residual current IPE |
≤ 400 µA |
Nominal discharge current In (8/20) µs (Core-Core) |
100 A |
Nominal discharge current In (8/20) µs (core-earth) |
2 kA (per signal pair) |
Total discharge current Itotal (8/20) µs |
10 kA |
Nominal pulse current Ian (10/700) µs (Core-Core) |
≤ 40 A |
Nominal pulse current Ian (10/700) µs (Core-Earth) |
≤ 160 A |
Output voltage limitation at 1 kV/µs (core-core) spike |
≤ 85 V (PoE) |
Output voltage limitation at 1 kV/µs (core-earth) spike |
≤ 700 V |
Output voltage limitation at 1 kV/µs (core-core) static |
≤ 9 V |
Output voltage limitation at 1 kV/µs (core-earth) static |
≤ 700 V |
Residual voltage at In (conductor-conductor) |
≤ 15 V |
≤ 100 V (PoE) |
Voltage protection level Up (core-core) |
≤ 9 V (B2 - 1 kV/25 A) |
≤ 100 V (B2 - 1 kV/25 A - PoE) |
≤ 15 V (500 V / 100 A) |
Voltage protection level Up (core-ground) |
≤ 900 V (B2 - 4 kV/100 A) |
≤ 700 V (C2 - 4 kV/2 kA) |
Response time tA (core-core) |
≤ 1 ns |
Response time tA (core-earth) |
≤ 100 ns |
Input attenuation aE, sym. |
≤ 1 dB (up to100 MHz/direct measuring) |
≤ 1 dB (up to 250 MHz/direct measuring) |
≤ 3 dB (up to 500 MHz/direct measuring) |
Near-end crosstalk attenuation |
≥ 35 dB (250 MHz/100 Ω/link) |
≥ 45 dB (100 MHz / 100 Ω / Link) |
≥ 27 dB (500 MHz / 100 Ω / Link) |
≥ 39 dB (250 MHz/100 Ω/direct measuring) |
Cut-off frequency fg (3 dB), sym. in 100 Ohm system |
> 500 MHz |
Capacity (core-core) |
typ. 12 pF (f= 1 MHz / VR= 0 V) |
Capacity (core-earth) |
typ. 2 pF (f= 1 MHz / VR= 0 V) |
Surge protection fault message |
None |
Impulse durability (conductor-conductor) |
B2 - 1 kV / 25 A |
Impulse durability (conductor-ground) |
B2 - 4 kV/100 A |
C2 - 4 kV/2 kA |
D1 - 1 kA |
General |
Housing material |
Zinc die-cast |
Color |
silver/black |
Mounting type |
Connection-specific attachment plug and DIN rail, 35 mm |
Design |
Attachment plug for DIN rail mounting |
Number of positions |
8 |
Direction of action |
Line-Line & Line-Ground/Shield |
Connection, equipotential bonding |
Connection method |
Cable connection |
Connection data |
Connection method |
RJ45 |
Connection method IN |
RJ45 socket |
Connection method OUT |
RJ45 socket |
Dimensions |
Height |
102 mm |
Width |
25 mm |
Depth |
63.5 mm |
|
Standards and Regulations |
Standards / specifications |
IEC 61643-21 2002 |
EN 50173-1 2002 |
ISO/IEC 11801-Am.1 2006 |
Environmental Product Compliance |
China RoHS |
Environmentally friendly use period: unlimited = EFUP-e |
Reach and RoHS Compliant |
Reach and RoHS Compliant |
Approvals |
|
UL Listed
EAC |
Commercial data |
Packing unit |
1 |
Weight per piece |
320.0 g |
Country of origin |
Germany |