PM-3133-100-CPS - CANOpen, 3 Phase Power Meter (60 A) by ICP DAS
|
|
|
3-phase power meter (60 A). Supports CANopen protocol. Current Measurements up to 200A with Different CT Ratio. Voltage up to 500V. Has operating temperatures of -10°C ~ +70°C (14°F ~ +158°F)
|
|
|
ICP DAS USA, Inc., brings powerful, cost-effective, advanced Smart Power Meters PM-3133-100-CPS model that gives you access to real-time electric usage for three-phase power measurement. With its high accuracy (<0.5%, PF=1 ), the PM-3133-160-CPS device can be applied to both low voltage primary side and/or medium/high voltage secondary side and enables the users to obtain reliable and accurate energy consumption readings from the monitored equipments in real time under operation. These compact size and cost-effective power meters are equipped with revolutionary wired clip-on CT (various types, support input current up to 200 A). It operates over a wide input voltages range 10 ~ 500 VAC which allows worldwide compatibility. And with 2 channels relay outputs, it can be linked with sirens or lightings for alarm messages. It also supports CANopen protocol for easy integration.
- True RMS Power Measurements
- Energy Analysis for 3P4W, 3P3W, 1P3W, 1P2W
- Current Measurements Up to 200 A with Different CT Ratio
- Voltage Measurements Up to 500 V
- Clip-on CT for Easy Installation
- W Accuracy Better than 0.5% (PF=1)
- Supports CANopen Protocol
- Supports 2 Power Relay Output (Form A)
PM-3133-100-CPS |
Wiring |
3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT |
Input Voltage |
10 ~ 300 V |
Input Current |
CTØ10 mm (60 A); CTØ16 mm (100 A); CTØ24 mm (200 A) |
Input Frequency |
50/60 Hz |
W Accuracy |
Better than 0.5% (PF=1) |
Power Parameter Measurement |
True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF) |
Data Update Rate |
1 Second |
Communication |
RS-485 |
Protocol |
- |
Baud rate |
- |
Data format |
- |
Isolation |
- |
Ethernet |
Protocol |
- |
PoE |
- |
CAN Bus |
Protocol |
CAN and CANopen |
Baud Rate |
125 k (default), 250 k, 500 k,
1 M; DIP Switch Selectable |
PoE |
2500 VDC |
Alarm Output |
Power Relay |
Form A (Normal Open) x 2; Relay Contact Voltage Range: 5 A @ 250 VAC (47 ~ 63Hz), 5 A @ 30 VDC |
Power |
Input Range |
+12 ~ 48 VDC |
Power Consumption |
4 W |
Mechanical |
Casing |
Plastic (Flammability UL 94V-0) |
Dimensions (W x L x H) |
127 mm x 105 mm x 33 mm |
Module Installation |
DIN-Rail Mounting |
CT Installation |
Clip-On |
Environment |
Operating Temperature |
-10°C ~ +70°C (+14°F ~ +158°F) |
Storage Temperature |
-25°C ~ +80°C (-13°F ~ +176°F) |
Ambient Relative Humidity |
10% ~ 90% RH, Non-condensing |
|
|