M-7005 - 8-channel Thermistor Analog Input and 6-channel Digital Output Data Acquisition Module, supports Modbus RTU and RS-485 by ICP DAS
|
|
|
8-channel Thermistor Analog Input and 6-channel Digital Output (NPN, Sink,
Open Collector to 30V) Data Acquisition Module, communicable over Modbus RTU and
RS-485. Supports operating temperatures between -25 to 75°C (-13F ~ 167F).
|
|
|
The M-7005 module provides cost-effective protection and conditioning for a
wide range of valuable industrial control signals and systems. It is
communicable in Modbus RTU and RS-485 protocols. The input type is configurable;
Users can select the type and range remotely by issuing commands from the host.
Fewer modules may be used for different applications. The user may mount the
modules on a DIN rail, panel or wall. Module has a screw-terminal block to
connect to the signals. M-7005 comes with FREE EZ Data Logger Software.
Analog Input |
Input Channels |
8 differential |
Input Type |
Thermistor |
Thermistor Type |
Precon ST-A3, Fenwell U, YSI L100, YSI L300, YSI L1000, YSI B2252, YSI
B3000,
YSI B5000, YSI B6000, YSI B10000, YSI H10000, YSI H30000, User-defined |
Resolution |
16-bits |
Sampling Rate |
8 samples/second (Total) |
Accuracy |
+/- 0.1% |
Zero Drift |
+/-20uV/°C |
Span Drift |
+/-25 ppm/°C |
Common Mode Rejection |
86dB |
Normal Mode Rejection |
100dB |
Voltage Input Impedance |
>1M Ohms |
Individual Channel Configurable |
Yes |
Open Wire Detection |
Yes |
Intra-module Isolation, Field to Logic |
3000 VDC |
Digital Output |
Output Channels |
6 |
Output Type |
NPN, Sink, Open Collector to 30V |
Output Load |
100mA max. per channel |
Interface |
Interface |
RS-485 |
Format |
N, 8, 1 |
Baud Rate |
1200~115200 bps |
LED Display |
1
LED |
as Power/ Communication indicator |
Power |
Input Voltage Range |
+10 ~ +30 Vdc |
Power Consumption |
1.3 W |
Protocol |
Support Modbus and DCON Protocol |
Yes |
Watchdog |
Yes, Module, Communication (Programmable over DCON) |
Environment |
Operating temperature |
-25 to 75°C |
Storage temperature |
-40 to 85°C |
Humidity |
5 to 95%, non-condensing |
|
|