M-7019R - 8-channel Thermocouple, Current and Voltage Analog Input Module, Communicates over RS-485 and Modbus RTU by ICP DAS
|
|
|
8-channel Universal Analog Input Data Acquisition Module, supports current
input, voltage input, and thermocouple input. Communicable over Modbus RTU,
RS-485 and DCON protocol. Comes with free EZ Data Logger software for data
logging. Supports operating temperatures between -25°C ~ +75°C (-13°F ~ +167°F)
|
|
|
The M-7019 is a 8-channel Universal Analog Input Data Acquisition Module,
supports current input, voltage input, and thermocouple input. Communicable over
Modbus RTU, RS-485 and DCON protocol. It comes with free EZ Data Logger software
for PC based data logging and monitoring systems. Supports operating
temperatures between -25°C ~ +75°C (-13°F ~ +167°F). The ICP DAS M-7000 family
of network data acquisition and control modules support Modbus RTU. They can be
remotely controlled using a set of commands called DCON protocol. With the
Modbus RTU protocol, it can easily communicate with most popular
- SCADA/HMI software and PLCs.
- Indication LED Light for power and communication
- Individual Channel Configurable
- Wire Opening Detection for Thermocouple
- Support Modbus and DCON Protocol
- Input Channels: 8 differential
- Communication Interface: RS-485
- Din Rail Mount
Communication |
Interface |
RS-485 |
Bias Resistor |
No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4
or SG-785.) |
Format |
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
Baud Rate |
1200 to 115200 bps |
Protocol |
Modbus RTU, DCON |
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicator/Display |
System LED Indicator |
Yes, 1 as Power/Communication Indicator |
I/O LED Indicators |
- |
7-Segment LED Display |
- |
Isolation |
Intra-module Isolation, Field-to-Logic |
3000 VDC |
EMS Protection |
ESD (IEC 61000-4-2) |
±4 kV |
EFT (IEC 610004-4) |
±4 kV |
Power |
Reverse Polarity Protection |
Yes |
Input Range |
+10 ~ +30 VDC |
Consumption |
1.2 W |
Mechanical |
Dimensions (L x W x H) |
123 mm x 72 mm x 35 mm |
Installation |
DIN-Rail or Wall Mounting |
Environment |
Operating Temperature |
-25°C ~ +75°C (-13°F ~ +167°F) |
Storage Temperature |
-40°C ~ +85°C (-40°F ~ +185°F) |
Humidity |
10 - 95% RH, Non-condensing |
I/O Specifications
Analaog Input |
Channels |
8 |
Wiring |
Differential |
Sensor Types |
Thermocouple |
J, K, T, E, R, S, B, N, C, L, M, LDIN43710 |
Voltage |
±15 mV, ±50 mV, ±100 mV, ±150 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, ±10 V |
Current |
±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (Jumper selectable) |
Resolution |
16-bit |
Accuracy |
0.1% of FSR |
Sampling Rate |
8 Hz (Total) |
Input Impedence |
Voltage |
2 MΩ |
Current |
125 Ω |
Thermocouple |
> 400 kΩ |
Common Voltage Protection |
±200 VDC |
Individual Channel Configuration |
Yes |
Overvoltage Protection |
240 Vrms |
Open Wire Detection (for thermocouple only) |
Yes |
Temperature Outputs Consistency |
- |
Stable Temperature Output in the Field |
- |
|
|