The M-7000 series is a family of network data acquisition and control modules
that support Modbus RTU. They can be remotely controlled using a set of commands
called DCON protocol. With the Modbus RTU protocol, it can easily communicate
with most popular SCADA/ HMI software and PLCs.
Counter Input
Channels
2 independent 32-bit counters, counter 0&1
Input Type
Isolated or non-isolated
Isolated Input Level
Logic level 0:+1V max.
Logic level 1: +3.5 to 30V
Isolation Voltage
3750Vrms
Non-Isolated Input Level (Programmable)
Logic level 0: 0 to +5V (default= 0.8V)
Logic level 1: 0 to +5V (default= 2.4V)
Maximum Count
32bit (4,294,967,295)
Programmable Digital Noise Filter
2us to 65ms
Alarming
alarm on counter 0 or counter 0 & 1, programmable
Counter Rreset Value
programmable
Built-in Virtual Battery Back Up
for Counter Value
Frequency Measurement
Input Frequency
1Hz to 100KHz max.
Gate Time
1.0 or 0.1sec, programmable
Digital Output
Channels
2
Output Type
Source, Open-Collector
Output Voltage
30V max.
Output Current
30mA max
Interface
Interface
RS-485
Format
N, 8, 1
Baud Rate
1200 ~ 115200bps
LED Display
1 LED
as Power/ Communication indicator
5-digit readout
Channel 0 or Channel 1 (for M-7080BD-G)
Power
Input Voltage Range
10~30VDC for M-7080 and
M-7080D, 24~30VDC for M-7080B and M-7080BD