Advantech ADAM-4012-DE - *Discontinued* - ANALOG INPUT MODULE W/2 D OUT by Advantech
|
|
|
|
- RS485 communications
- Software Configuration and Calibration
- Watchdog Timer
- nput type: Thermocouple, mV, V or mA
- RTD modules with models supporting Modbus
- Serial Based Dual Loop PID Controller with Modbus
- Isolation voltage: 3000 VDC
- Power input from 10 to 30 VDC
- ADAM Series Utility software
- ADAM Isolated RS-232/RS-485 Converter (optional)
|
|
|
ADAM-4012-DE The ADAM-4000 series is a set of intelligent sensor-to-computer interface analog I/O modules containing a built-in microprocessor. They are remotely controlled through a simple set of commands issued in ASCII format and transmitted in RS-485 protocol.
The 4000 series provide signal conditioning, isolation, ranging, A/D and D/A conversion, data comparison, and digital communication functions. Some modules provide digital I/O lines for controlling relays and TTL devices.
Buy and compare our RS-485 I/O modules below. Click on each model number to view a photo and see the Details, Specs, Documentation, and Accessories tabs for further information.
General
- Power Consumption 1.2 W @ 24 VDC
- Supported Protocols ASCII command
- Connectors 1 x plug-in terminal block (#14 ~ 22 AWG)
Analog Input
- Channels 1
- Input Impedance Voltage: 20 MΩ Current: 125 Ω (Added by user)
- Input Type mV, V or mA
- Input Range ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V and ±20 mA
- Accuracy Voltage mode: ±0.1% or better Current mode: ±0.2% or better
- Span Drift ±25 ppm/°C
- Zero Drift ±6 µV/°C
Digital Input
- Channels 1 Logic level 0: 1 V max. Logic level 1: 3.5 ~ 30 V pull up current: 0.5 mA, 10 kΩ resistor to 5 V
- Event Counter Max. input freq.: 50 Hz Min. input pulse width: 1 msec.
Digital Output
- Channels 2, open collector to 30 V, 30 mA max. load
- Power Dissipation 300 mW
|
|
|
|