Advantech ADAM-4019+ - *Discontinued* - 8 CHANNEL UNIVERSAL ANALOG INPUT W/MODBUS SUPPORT by Advantech
|
|
|
|
- Supports 4~20 mA
- Software configurable for mV, V, mA or Thermocouple inputs
- 16-bit resolution
- Isolation voltage 3000 VDC
- Supports Modbus/RTU Protocol
- Burn-out detection function
|
|
|
ADAM-4019+ is an 8-channel Universal Analog Input Module. The new module improves over its predecessor ADAM-4019 with a 4~20 mA input range, and a burnout detection function. Its mixed input range design supports individual configuration for each channel to save costs and space in applications. The other frequently used input ranges include +/-10V, mV, and thermocouple, which are all well-integrated in this model. It also supports burnout detection so that any sensor failures can be detected in advance. For easier control, ADAM-4019+ provides not only ADAM ASCII commands, but also the Modbus/RTU protocol for satisfying different application demands.
General
- Power Consumption: 1.0 W @ 24 VDC
- Watchdog Timer: System (1.6 second) & Communication
- Supported Protocols: ASCII command and Modbus/RTU
Analog Input
- Channels: 8 differential channels for individual input type
- Channel Independent Configuration: Yes
- Input Impedance: Voltage: 20 MΩ Current: 120 Ω
- Input Type: T/C, mV, V, mA
- Voltage/Current Input Range: ±1 V, ±2.5 V, ±5 V, ±10 V, ±100 mV, ±500 mV, ±20 mA, 4 ~ 20 mA
- T/C Types and Temperature Ranges
J |
0 ~ 760 °C |
R |
500 ~ 1,750 °C |
K |
0 ~ 1370 °C |
S |
500 ~ 1,750 °C |
T |
- 100 ~ 400 °C |
B |
500 ~ 1,800 °C |
E |
0 ~ 1,000 °C |
|
|
- Burn-out Detection: 4 ~ 20 mA & all T/C
|
|
|
|