Need assistance or guidance?

Contact us @: 1-800-301-9097
Login / Register Contact Us
 
I-7015 - 6 channels of RTD module by ICP DAS

I-7015 - 6 channels of RTD module
by ICP DAS

Write a review Write a review

3 wire RTD (Resistance Temperature Detector) Input Data Acquisition Module with 6 Analog Input Channels, communicable over RS-485, and FREE EZ Data Logger Software. Supports operating temperatures between -25°C ~ +75°C (-13°F ` +167°F).

Mfg SKU # : I-7015
List Price : $489.00
Our Price : $480.00
Stock : Call for Availability
Quantity :

The I-7000 series is a family of network data acquisition and control modules, providing analog-to-digital, digitalto-analog, digital input/output, timer/counter and other functions. The modules can be remotely controlled using a set of commands, which we call the DCON protocol. Communication between the module and the host is in ASCII format via an RS-485 bi-directional serial bus standard. Baud Rates are software programmable and transmission speeds of up to 115.2 Kbps can be selected. I-7015 is intelligently designed to provide signal conditioning system monitoring and safe value settings.

I-7015 is a cost-effective solution for a wide range of valuable industrial control signals and systems. The DCON utility can help users to configure and test I-7015 RTD Input modules. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals. I-7015 comes with FREE EZ Data Logger Software.

i-7015 block diagram

Analog Input
Input Channels 6
Input Type Supports 2/3 wire RTD
Wire connection 2/3 wire
RTD Type Pt100, Pt1000, Ni120, Cu100, Cu1000
Resolution 16-bit
Sampling Rate 12 samples/ second (Total)
Accuracy +/-0.05%
-3dB BandWidth 5.24Hz
Common Mode Rejection Typical 86dB
Voltage Input Impedance >1M Ohms
Open Wire Detection Yes
Individual Channel Configurable Yes
Isolation Voltage 3000 VDC
Communication Interface
Interface RS-485
Power Supply
Input +10 to +30 Vdc
Power Consumption 1.1W
Mount
Din Rail Mount Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RTD Type Setting (TT)
Type
Code
RTD Type Temperature Range °C
 20  Platinum 100,α= 0.00385  -100 ~ 100
 21  Platinum 100, α= 0.00385   0 ~ 100
 22  Platinum 100, α= 0.00385  0 ~ 200
 23  Platinum 100, α= 0.00385  0 ~ 600
 24  Platinum 100, α= 0.003916  -100 ~ 100
 25  Platinum 100, α= 0.003916  0 ~ 100
 26  Platinum 100, α= 0.003916  0 ~ 200
 27  Platinum 100, α= 0.003916  0 ~ 600
 28  Nickel 120  -80 ~ 100
 29  Nickel 120  0 ~ 100
 2A  Platinum 1000, α= 0.00385  -200 ~ 600
 2B  Cu 100 at 0°C, α= 0.00421  -20 ~ 150
 2C  Cu 100 at 25°C, α= 0.00427  0 ~ 200
 2D  Cu 1000 at 0°C,α= 0.00421  -20 ~ 150

 

I-7015.pdf357 K

Copyright © 2024 iComTech. All rights reserved. Shopping Cart Software powered by ecMidas.