Power Relay Output & Isolated Digital Input (Counters) Data Acquisition Module communicable over RS-485. Supports operating temperatures between -25°C ~ +75°C (-13°F ~ +167°F).
I-7063D is intelligently designed to provide signal conditioning system monitoring and safe value settings. I-7063D is a cost-effective solution for a wide range of valuable industrial control signals and systems. The DCON utility can help users to configure and test I-7063 Power relay output module. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. The communication interface is modbus protocol via RS-485. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals.
Digital Input
Channels
8
Input Type
Sink, Source, isolated channels with common ground or power
Off Voltage Level
+1V max.
On Voltage Level
+4 to +30V
Input Impedance
3K Ohms, 0.5W
Counters
channels : 8
Max. Counts: 16-bit (65535)
Max. Input Frequency : 100Hz
Min. Pulse Width : 5ms
Photo-Isolation
3750Vrms
Relay Output
Channels
3
Relay Type
Form "A” relay SPST (N.O.)
Contact Rating
AC: 250V @5A
DC: 30V @5A
Operating Time(Max.)
6ms
Release Time(Min.)
3ms
Surge Strength
4,000VAC
Insulation Resistance
1000MOhms min. at 500VDC
Life Time
Mechanical : 20 X 10^6 OPS
Electrical : 100 X 10^3 Full Load
Interface
Interface
RS-485
Format
N, 8, 1
Baud Rate
1200 ~ 115200bps
LED Display
1 LED as Power/ Communication indicator
8 LEDs as Digital Input indicators and 3 LEDs as Relay Output indicators (for I-7063D)