| ioLogik E2214 Specifications |
| • Inputs and Outputs |
| Digital Inputs |
6 channels |
| Relay Outputs |
6 channels |
| Isolation |
3k VDC or 2k Vrms |
| • Digital Input |
| Sensor Type |
Wet Contact (NPN or PNP) and Dry Contact |
| I/O Mode |
DI or Event Counter |
| Dry Contact |
• On: short to GND
• Off: open |
| Wet Contact (DI to GND) |
• On: 0 to 3 VDC
• Off: 10 to 30 VDC |
| Common Type |
3 points per COM |
| Counter Frequency |
900 Hz |
| Digital Filtering Time Interval |
Software Configurable |
| • Relay Output |
| Type |
Form A (N.O.) power relay |
| Contact Current Rating |
• Inductive Load: 2 A @ 30 VDC, 250 VAC, 110 VAC
• Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC |
| Minimum permitted load |
1 A @ 5 VDC |
| Initial Insulation Resistance |
1000 M ohms (min.) @ 500 VDC |
| Mechanical endurance |
1,000,000 operationsElectrical endurance: 100,000 operations @ 5 A resistive load |
| Contact Resistance |
100 m ohms (max.) |
| Pulse Output |
0.3 Hz at rated load |
| • Power Requirements |
| Power Consumption |
170 mA @ 24 VDC |
| • MTBF (mean time between failures) |
| Time |
307,239 hrs |
| Database |
Telcordia (Bellcore) |
| Common Specifications |
| • LAN |
| Ethernet |
1 10/100 Mbps RJ45 port |
| Protection |
1.5 kV magnetic isolation |
| Protocols |
Modbus/TCP, TCP/IP, UDP, DHCP, BOOTP, SNMP, HTTP, CGI, SNTP, SMTP |
| • Serial Communication |
| Interface |
RS-485-2w: Data+, Data-, GND (3-contact terminal block) |
| Serial Line Protection |
15 kV ESD for all signals |
| • Serial Communication Parameters |
| Parity |
None |
| Data Bits |
8 |
| Stop Bits |
1 |
| Flow Control |
None |
| Baudrate |
1200 to 115200 bps |
| Protocol |
Modbus/RTU |
| • Power Requirements |
| Power Input |
24 VDC nominal, 12 to 36 VDC |
| • Physical Characteristics |
| Wiring |
I/O cable max. 14 AWG |
| Dimensions |
115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in) |
| Weight |
under 250 g |
| Mounting |
DIN rail or wall |
| • Environmental Limits |
| Operating Temperature |
Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
| Storage Temperature |
-40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity |
5 to 95% (non-condensing) |
| Altitude |
Up to 2000 m |
| Note |
Please contact Moxa if you require products guaranteed to function properly at higher altitudes. |
| • Standards and Certifications |
| Safety |
UL 508 |
| EMI |
EN 61000-3-2; EN 61000-3-3; EN 61000-6-4;
FCC Part 15, Subpart B, Class A |
| EMS |
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
EN 61000-4-5, EN 61000-4-6, EN 61000-4-8,
EN 61000-4-11, EN 61000-6-2 |
| Shock |
IEC 60068-2-27 |
| Freefall |
IEC 60068-2-32 |
| Vibration |
IEC 60068-2-6 |
| Green Product |
RoHS, CRoHS, WEEE |
| Note |
Please check Moxa’s website for the most up-to-date certification status. |