Environmental Product Compliance |
REACH SVHC |
Lead 7439-92-1 |
China RoHS |
Environmentally Friendly Use Period = 25; |
General |
Net weight |
1.5 kg |
Efficiency |
> 93 % (for 230 V AC and nominal values) |
Insulation voltage input/output |
3 kV AC (type test) |
|
1.5 kV AC (routine test) |
Protection class |
I (in closed control cabinet) |
Degree of protection |
IP20 |
MTBF (IEC 61709, SN 29500) |
> 1800000 h (25 °C) |
|
> 1000000 h (40 °C) |
|
> 480000 h (60 °C) |
Mounting position |
horizontal DIN rail NS 35, EN 60715 |
Assembly instructions |
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
Standards and Regulations |
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Noise emission |
EN 55011 (EN 55022) |
Noise immunity |
EN 61000-6-2:2005 |
Standards/regulations |
EN 61000-4-2 |
Contact discharge |
4 kV (Test Level 2) |
Standards/regulations |
EN 61000-4-3 |
Frequency range |
80 MHz ... 1 GHz |
Test field strength |
10 V/m (Test Level 3) |
Frequency range |
1.4 GHz ... 2 GHz |
Test field strength |
3 V/m (Test Level 2) |
Standards/regulations |
EN 61000-4-4 |
Comments |
Criterion B |
Standards/regulations |
EN 61000-6-3 |
|
EN 61000-4-6 |
Frequency range |
0.15 MHz ... 80 MHz |
Voltage |
10 V (Test Level 3) |
Low Voltage Directive |
Conformance with LV directive 2006/95/EC |
Standard - Safety of transformers |
EN 61558-2-16 (air clearances and creepage distances only) |
Standard - Electrical safety |
IEC 60950-1/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations |
EN 50178/VDE 0160 (PELV) |
Standard – Safety extra-low voltage |
IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
Standard - Safe isolation |
DIN VDE 0100-410 |
Standard – Limitation of mains harmonic currents |
EN 61000-3-2 |
UL approvals |
UL Listed UL 508 |
|
UL/C-UL Recognized UL 60950-1 |
Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
|
15 Hz ... 150 Hz, 4g, 90 min. |
Rail applications |
EN 50121-4 |
GL |
GL applied for |
Connection data, input |
Connection method |
Push-in connection |
Conductor cross section solid min. |
0.2 mm² |
Conductor cross section solid max. |
4 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
2.5 mm² |
Conductor cross section AWG min. |
24 |
Conductor cross section AWG max. |
12 |
Stripping length |
10 mm |
Output data |
Nominal output voltage |
24 V DC ±1 % |
Setting range of the output voltage (USet) |
24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) |
20 A |
Dynamic Boost (IDyn.Boost) |
30 A (5 s) |
Derating |
> 60 °C ... 70 °C (2.5%/K) |
Connection in parallel |
Yes, for redundancy and increased capacity |
Connection in series |
yes |
Feedback resistance |
≤ 35 V DC |
Protection against surge voltage on the output |
≤ 30 V DC |
Control deviation |
< 1 % (change in load, static 10 % ... 90 %) |
|
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) |
|
< 0.1 % (change in input voltage ±10 %) |
Residual ripple |
< 30 mVPP (with nominal values) |
Output power |
480 W |
Typical response time |
< 1 s |
Maximum power dissipation in no-load condition |
< 5.7 W |
Power loss nominal load max. |
< 44 W |
Connection data for signaling |
Connection method |
Push-in connection |
Conductor cross section solid min. |
0.2 mm² |
Conductor cross section solid max. |
1.5 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
1.5 mm² |
Conductor cross section AWG min. |
24 |
Conductor cross section AWG max. |
16 |
Stripping length |
8 mm |
Dimensions |
Width |
68 mm |
Height |
130 mm |
Depth |
160 mm |
Weight per piece |
1675.8 GRM |
Input data |
Nominal input voltage range |
100 V AC ... 240 V AC |
|
110 V DC ... 250 V DC |
Input voltage range |
100 V AC ... 240 V AC -15 % ... +10 % |
|
99 V DC ... 275 V DC |
Dielectric strength maximum |
≤ 300 V AC 15 s |
AC frequency range |
50 Hz ... 60 Hz ±10 % |
Discharge current to PE |
< 3.5 mA |
Current consumption |
5.6 A (100 V AC) |
|
4.3 A (120 V AC) |
|
2.4 A (230 V AC) |
|
2.4 A (240 V AC) |
Nominal power consumption |
534.7 VA |
Inrush surge current |
≤ 20 A (typical) |
Mains buffering |
typ. 10 ms (120 V AC) |
|
typ. 15 ms (230 V AC) |
Input fuse |
10 A (internal (device protection)) |
Choice of suitable circuit breakers |
10 A ... 16 A (Characteristics B, C, D, K) |
Power factor (cos phi) |
0.98 |
Type of protection |
Transient surge protection |
Protective circuit/component |
Varistor |
Connection data, onput |
Connection method |
Push-in connection |
Conductor cross section solid min. |
0.2 mm² |
Conductor cross section solid max. |
10 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
6 mm² |
Conductor cross section AWG min. |
24 |
Conductor cross section AWG max. |
8 |
Stripping length |
15 mm |
Ambient conditions |
Degree of protection |
IP20 |
Ambient temperature (operation) |
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (start-up type tested) |
-40 °C |
Ambient temperature (storage/transport) |
-40 °C ... 85 °C |
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
Climatic class |
3K3 (in acc. with EN 60721) |
Degree of pollution |
2 |
Installation height |
≤ 4000 m (> 2000 m, Derating: 10 %/1000 m) |
Approvals |
|
- cULus Listed
- DNV GL
- cULus Recognized
- EAC
- UL Recognized
- cUL Recognized
- cUL Listed
- IECEE CB Scheme
- UL Listed
|