TRIO-PS-2G/3AC/24DC/5 - 29031538 |
TRIO-PS-2G/3AC/24DC/10 - 29031548 |
TRIO-PS-2G/3AC/24DC/20 - 29031558 |
TRIO-PS-2G/3AC/24DC/40 - 29031568 |
Environmental Product Compliance |
China RoHS |
Environmentally Friendly Use Period = 25; |
Environmentally Friendly Use Period = 25; |
Environmentally Friendly Use Period = 25; |
Environmentally Friendly Use Period = 25; |
REACH SVHC |
|
|
Lead 7439-92-1 |
Lead 7439-92-1 |
General |
Net weight |
0.4 kg |
0.9 kg |
1.5 kg |
2.6 kg |
Efficiency |
> 91 % (at 400 V AC and nominal values) |
> 92 % (at 400 V AC and nominal values) |
> 93 % (400 V AC) |
typ. 93 % (400 V AC) |
Insulation voltage input/output |
3 kV AC (type test) |
3 kV AC (type test) |
3 kV AC (type test) |
3 kV AC (type test) |
|
1.5 kV AC (routine test) |
1.5 kV AC (routine test) |
1.5 kV AC (routine test) |
1.5 kV AC (routine test) |
Protection class |
II (in closed control cabinet) |
I (in closed control cabinet) |
I (in closed control cabinet) |
I (in closed control cabinet) |
Degree of protection |
IP20 |
IP20 |
IP20 |
IP20 |
MTBF (IEC 61709, SN 29500) |
> 2300000 h (25 °C) |
> 2100000 h (25 °C) |
> 1800000 h (25 °C) |
> 1730000 h (25 °C) |
|
> 1300000 h (40 °C) |
> 1200000 h (40 °C) |
> 1100000 h (40 °C) |
> 1051000 h (40 °C) |
|
> 620000 h (60 °C) |
> 590000 h (60 °C) |
> 510000 h (60 °C) |
> 510000 h (60 °C) |
Mounting position |
horizontal DIN rail NS 35, EN 60715 |
horizontal DIN rail NS 35, EN 60715 |
horizontal DIN rail NS 35, EN 60715 |
horizontal DIN rail NS 35, EN 60715 |
Assembly instructions |
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
Efficiency |
|
|
500 V AC |
typ. 93.3 % (480 V AC) |
Standards and Regulations |
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Conformance with EMC Directive 2014/30/EU |
Conformance with EMC Directive 2014/30/EU |
Conformance with EMC Directive 2014/30/EU |
Noise emission |
EN 55011 (EN 55022) |
EN 55011 (EN 55022) |
EN 55011 (EN 55022) |
EN 55011 (EN 55022) |
Noise immunity |
Immunity according to EN 61000-6-2 (industrial) |
Immunity according to EN 61000-6-2 (industrial) |
Immunity according to EN 61000-6-2 (industrial) |
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial) |
Standards/regulations |
EN 61000-4-2 |
EN 61000-4-2 |
EN 61000-4-2 |
EN 61000-4-2 |
Contact discharge |
4 kV (Test Level 2) |
4 kV (Test Level 2) |
4 kV (Test Level 2) |
4 kV (Test Level 2) |
Standards/regulations |
EN 61000-4-3 |
EN 61000-4-3 |
EN 61000-4-3 |
EN 61000-4-3 |
Frequency range |
80 MHz ... 1 GHz |
80 MHz ... 1 GHz |
80 MHz ... 1 GHz |
80 MHz ... 1 GHz |
Test field strength |
10 V/m (Test Level 3) |
10 V/m (Test Level 3) |
10 V/m (Test Level 3) |
10 V/m (Test Level 3) |
Frequency range |
1.4 GHz ... 2 GHz |
1.4 GHz ... 2 GHz |
1.4 GHz ... 2 GHz |
1.4 GHz ... 2 GHz |
Test field strength |
3 V/m (Test Level 2) |
3 V/m (Test Level 2) |
3 V/m (Test Level 2) |
3 V/m (Test Level 2) |
Standards/regulations |
EN 61000-4-4 |
EN 61000-4-4 |
EN 61000-4-4 |
EN 61000-4-4 |
Comments |
Criterion B |
Criterion B |
Criterion B |
Criterion B |
Standards/regulations |
EN 61000-6-3 |
EN 61000-6-3 |
EN 61000-6-3 |
EN 61000-6-3 |
|
EN 61000-4-6 |
EN 61000-4-6 |
EN 61000-4-6 |
EN 61000-4-6 |
Frequency range |
0.15 MHz ... 80 MHz |
0.15 MHz ... 80 MHz |
0.15 MHz ... 80 MHz |
0.15 MHz ... 80 MHz |
Voltage |
10 V (Test Level 3) |
10 V (Test Level 3) |
10 V (Test Level 3) |
10 V (Test Level 3) |
Conducted noise emission |
EN 55016 EN 61000-6-4 (Class A) |
EN 55016 EN 61000-6-4 (Class A) |
EN 55016 EN 61000-6-4 (Class A) |
EN 55016 EN 61000-6-4 (Class A) |
Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
Conformance with Low Voltage Directive 2014/35/EC |
Conformance with Low Voltage Directive 2014/35/EC |
Conformance with Low Voltage Directive 2014/35/EC |
Standard - Safety of transformers |
EN 61558-2-16 (air clearances and creepage distances only) |
EN 61558-2-16 (air clearances and creepage distances only) |
EN 61558-2-16 (air clearances and creepage distances only) |
|
Standard - Electrical safety |
IEC 60950-1/VDE 0805 (SELV) |
IEC 60950-1/VDE 0805 (SELV) |
IEC 60950-1/VDE 0805 (SELV) |
IEC 60950-1/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations |
EN 50178/VDE 0160 (PELV) |
EN 50178/VDE 0160 (PELV) |
EN 50178/VDE 0160 (PELV) |
EN 50178/VDE 0160 (PELV) |
Standard – Safety extra-low voltage |
IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
Standard - Safe isolation |
DIN VDE 0100-410 |
DIN VDE 0100-410 |
DIN VDE 0100-410 |
DIN VDE 0100-410 |
Standard – Limitation of mains harmonic currents |
EN 61000-3-2 |
EN 61000-3-2 |
EN 61000-3-2 |
EN 61000-3-2 |
UL approvals |
UL Listed UL 508 |
UL Listed UL 508 |
UL Listed UL 508 |
UL Listed UL 508 |
|
UL/C-UL Recognized UL 60950-1 |
UL/C-UL Recognized UL 60950-1 |
UL/C-UL Recognized UL 60950-1 |
UL/C-UL Recognized UL 60950-1 |
Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
11 ms, 15g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
DNV GL CG-0339 / Class B 2 Hz - 100 Hz resonance search, 90 min. in resonance, 2 Hz - 13.2 Hz, ±1 mm amplitude, 13.2 Hz - 100 Hz, 0.7g acceleration |
|
15 Hz ... 150 Hz, 4g, 90 min. |
15 Hz ... 150 Hz, 4g, 90 min. |
15 Hz ... 150 Hz, 4g, 90 min. |
|
Rail applications |
EN 50121-4 |
EN 50121-4 |
EN 50121-4 |
EN 50121-4 |
Shipbuilding approval |
|
|
GL applied for |
|
Standards/regulations |
|
|
|
EN 61000-4-11 |
Overvoltage category (EN 60950-1) |
|
|
|
II |
Overvoltage category (EN 62477-1) |
|
|
|
III |
Connection data, input |
Connection method |
Push-in connection |
Push-in connection |
Push-in connection |
Push-in connection |
Conductor cross section solid min. |
0.2 mm² |
0.2 mm² |
0.2 mm² |
0.2 mm² |
Conductor cross section solid max. |
4 mm² |
4 mm² |
4 mm² |
4 mm² |
Conductor cross section flexible min. |
0.2 mm² |
0.2 mm² |
0.2 mm² |
0.2 mm² |
Conductor cross section flexible max. |
2.5 mm² |
2.5 mm² |
2.5 mm² |
2.5 mm² |
Conductor cross section AWG min. |
24 |
24 |
24 |
24 |
Conductor cross section AWG max. |
12 |
12 |
12 |
12 |
Stripping length |
10 mm |
10 mm |
10 mm |
10 mm |
Output data |
Nominal output voltage |
24 V DC ±1 % |
24 V DC ±1 % |
24 V DC ±1 % |
24 V DC ±1 % |
Setting range of the output voltage (USet) |
24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) |
5 A |
10 A |
20 A |
40 A |
Dynamic Boost (IDyn.Boost) |
7.5 A (5 s) |
15 A (5 s) |
30 A (5 s) |
60 A (5 s) |
Derating |
> 60 °C ... 70 °C (2.5%/K) |
> 60 °C ... 70 °C (2.5%/K) |
> 60 °C ... 70 °C (2.5%/K) |
> 60 °C ... 70 °C (2.5%/K) |
Connection in parallel |
Yes, for redundancy and increased capacity |
Yes, for redundancy and increased capacity |
Yes, for redundancy and increased capacity |
Yes, for redundancy and increased capacity |
Connection in series |
yes |
yes |
yes |
yes |
Protection against surge voltage on the output |
≤ 30 V DC |
≤ 30 V DC |
≤ 30 V DC |
≤ 30 V DC |
Control deviation |
< 1 % (change in load, static 10 % ... 90 %) |
< 1 % (change in load, static 10 % ... 90 %) |
< 1 % (change in load, static 10 % ... 90 %) |
< 1 % (change in load, static 10 % ... 90 %) |
|
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) |
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) |
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) |
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) |
|
< 0.1 % (change in input voltage ±10 %) |
< 0.1 % (change in input voltage ±10 %) |
< 0.1 % (change in input voltage ±10 %) |
< 0.1 % (change in input voltage ±10 %) |
Residual ripple |
≤ 20 mVPP |
≤ 20 mVPP |
≤ 20 mVPP |
≤ 50 mVPP |
Output power |
120 W |
240 W |
480 W |
960 W |
Typical response time |
< 1 s |
< 1 s |
< 1 s |
< 1 s |
Maximum power dissipation in no-load condition |
< 1 W (400 V AC) |
< 1.1 W (400 V AC) |
< 1.2 W (400 V AC) |
< 14 W (400 V AC) |
Power loss nominal load max. |
< 12 W (480 V AC) |
< 22 W (480 V AC) |
< 38 W (480 V AC) |
< 68 W (480 V AC) |
Feedback resistance |
|
|
|
< 35 V |
Short-circuit current |
|
|
|
< (Permanent) |
Connection data for signaling |
Connection method |
Push-in connection |
Push-in connection |
Push-in connection |
Push-in connection |
Conductor cross section solid min. |
0.2 mm² |
0.2 mm² |
0.2 mm² |
0.2 mm² |
Conductor cross section solid max. |
1.5 mm² |
1.5 mm² |
1.5 mm² |
1.5 mm² |
Conductor cross section flexible min. |
0.2 mm² |
0.2 mm² |
0.2 mm² |
0.2 mm² |
Conductor cross section flexible max. |
1.5 mm² |
1.5 mm² |
1.5 mm² |
1.5 mm² |
Conductor cross section AWG min. |
24 |
24 |
24 |
24 |
Conductor cross section AWG max. |
16 |
16 |
16 |
16 |
Stripping length |
8 mm |
8 mm |
8 mm |
8 mm |
Dimensions |
Width |
35 mm |
42 mm |
65 mm |
110 mm |
Height |
130 mm |
130 mm |
130 mm |
130 mm |
Depth |
115 mm |
160 mm |
160 mm |
160 mm |
Weight per piece |
568.5 GRM |
1070.0 GRM |
1717.0 GRM |
2850.0 GRM |
Input data |
Nominal input voltage range |
3x 400 V AC ... 500 V AC |
3x 400 V AC ... 500 V AC |
3x 400 V AC ... 500 V AC |
3x 400 V AC ... 500 V AC |
|
2x 400 V AC ... 500 V AC |
2x 400 V AC ... 500 V AC |
2x 400 V AC ... 500 V AC |
|
Input voltage range |
3x 400 V AC ... 500 V AC -20 % ....+15 % |
3x 400 V AC ... 500 V AC -20 % ....+15 % |
3x 400 V AC ... 500 V AC -20 % ....+15 % |
3x 400 V AC ... 500 V AC -20 % ....+15 % |
|
2x 400 V AC ... 500 V AC -10 % ... +15 % |
2x 400 V AC ... 500 V AC -10 % ... +15 % |
2x 400 V AC ... 500 V AC -10 % ... +15 % |
|
AC frequency range |
50 Hz ... 60 Hz |
50 Hz ... 60 Hz |
50 Hz ... 60 Hz |
50 Hz ... 60 Hz |
Discharge current to PE |
< 0.25 mA |
< 3.5 mA |
< 3.5 mA |
< 3.5 mA |
Current consumption |
3x 0.4 A (400 V AC) |
3x 0.6 A (400 V AC) |
3x 1.2 A (400 V AC) |
3x 1.9 A (400 V AC) |
|
3x 0.3 A (500 V AC) |
3x 0.6 A (500 V AC) |
3x 1 A (500 V AC) |
3x 1.7 A (500 V AC) |
|
2x 0.6 A (400 V AC) |
2x 1.1 A (400 V AC) |
2x 2.3 A (400 V AC) |
|
|
2x 0.5 A (500 V AC) |
2x 1.1 A (500 V AC) |
2x 1.9 A (500 V AC) |
|
Nominal power consumption |
243.6 VA |
451.7 VA |
822.2 VA |
1335.1 VA |
Inrush surge current |
≤ 22 A (typical) |
≤ 26 A (typical) |
≤ 22 A (typical) |
≤ (typical) |
Mains buffering |
typ. 20 ms (400 V AC) |
typ. 10 ms (400 V AC) |
typ. 10 ms (400 V AC) |
typ. 10 ms (400 V AC) |
|
typ. 20 ms (500 V AC) |
typ. 20 ms (500 V AC) |
typ. 20 ms (500 V AC) |
typ. 20 ms (500 V AC) |
Input fuse |
3.15 A (internal (device protection), slow-blow) |
3.15 A (internal (device protection), slow-blow) |
3.15 A (internal (device protection), slow-blow) |
6.3 A (internal (device protection)) |
Choice of suitable circuit breakers |
6 A ... 16 A (Characteristics B, C, D, K) |
6 A ... 16 A (Characteristics B, C, D, K) |
6 A ... 16 A (Characteristics B, C, D, K) |
10 A ... 16 A (Characteristics B, C, D, K) |
Power factor (cos phi) |
0.55 |
0.58 |
0.63 |
0.77 |
Type of protection |
Transient surge protection |
Transient surge protection |
Transient surge protection |
Transient surge protection |
Protective circuit/component |
Varistor |
Varistor |
Varistor |
Varistor |
Connection data, output |
Connection method |
Push-in connection |
Push-in connection |
Push-in connection |
Push-in connection |
Conductor cross section solid min. |
0.2 mm² |
0.2 mm² |
0.2 mm² |
0.75 mm² |
Conductor cross section solid max. |
4 mm² |
4 mm² |
10 mm² |
16 mm² |
Conductor cross section flexible min. |
0.2 mm² |
0.2 mm² |
0.2 mm² |
0.75 mm² |
Conductor cross section flexible max. |
2.5 mm² |
2.5 mm² |
6 mm² |
10 mm² |
Conductor cross section AWG min. |
24 |
24 |
24 |
20 |
Conductor cross section AWG max. |
12 |
12 |
8 |
4 |
Stripping length |
10 mm |
10 mm |
15 mm |
18 mm |
Ambient conditions |
Degree of protection |
IP20 |
IP20 |
IP20 |
IP20 |
Ambient temperature (operation) |
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (storage/transport) |
-40 °C ... 85 °C |
-40 °C ... 85 °C |
-40 °C ... 85 °C |
-40 °C ... 85 °C |
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
≤ 95 % (at 25 °C, non-condensing) |
≤ 95 % (at 25 °C, non-condensing) |
≤ 95 % (at 25 °C, non-condensing) |
Climatic class |
3K3 (in acc. with EN 60721) |
3K3 (in acc. with EN 60721) |
3K3 (in acc. with EN 60721) |
3K3 (in acc. with EN 60721) |
Degree of pollution |
2 |
2 |
2 |
2 |
Installation height |
≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
≤ 4000 m (> 2000 m, Derating: 10 %/1000 m) |
Ambient temperature (start-up type tested) |
|
-40 °C |
-40 °C |
-40 °C |
Approvals |
|
- DNV GL
- cULus Listed
- cULus Recognized
- EAC
- UL Recognized
- cUL Recognized
- cUL Listed
- IECEE CB Scheme
- UL Listed
|