Model Name |
TS2250B |
Topology |
Line-Interactive, Low Frequency |
On-battery Output Waveform |
Simulated Sine Wave |
Maximum Capacity (VA / W) |
2000VA / 1200W |
INPUT |
Nominal Input Voltage |
110 / 120 or 220 / 230 / 240Vac(!!) |
Nominal Input Frequency |
50Hz / 60Hz Auto Sensing |
Input Voltage Range |
Rated Voltage ±25% |
OUTPUT |
Nominal Output Voltage |
110 / 120 or 220 / 230 / 240Vac(!!) |
Output Voltage Regulation |
Rated Voltage ±5% (on battery) |
Transfer Time(Typical) |
4 ms |
Start on Battery |
Yes |
Auto Restart |
Yes |
Automatic Voltage Regulation (AVR) |
AVR increases the output voltage by 15% while the input voltage decreases by 9 % to 25 % |
AVR decreases the output voltage by 13% while the input voltage increases by 9 % to 25 % |
Number of Outlets |
5 Battery backup (IEC 10A) |
5 Battery backup (NEMA 15A) |
PROTECTION |
Data Line Surge Protection |
RJ11 / RJ45 |
Surge Energy Rating |
1185 Joules (NEMA modules) |
Overload Protection |
UPS shuts down at 110% load ater 60 secs or 130% load after 3 secs |
Over Current Protection |
Fuse (Circuit breakers for TS1250 / 1700 models with NEMA outlets) |
Discharge Protection |
Keylock |
BATTERY |
Configuration |
24V (12V 34W×2) |
Typical Backup Time** |
45 min |
Recharge Time to 90% (Typical) |
< 4 Hours |
ADVANCED WARNINGS / DIAGNOSTICS |
Front Panel LEDs |
AC Mode / Battery Mode / Battery Fault / Overload |
Audible Alarms |
Battery Mode / Battery Low / Overload |
COMMUNICATION INTERFACE |
Communication Port |
RS232 *2 for 220 / 230 / 240V models |
USB*1 for 110 / 120V models |
ENVIRONMENTAL |
Operation Temperature |
0~40°C / 32~104°F |
Storage Temperature |
-20~60°C / -4~140°F |
Relative Humidity |
0~95% Non condensing |
Audible Noise |
< 40 dBA |
PHYSICAL |
Dimensions
Physical / Packing (L×W×H) |
in |
15×5.1×7.5 / 19.1×9.6×12.2 |
mm |
382×130×192 / 485×244×310 |
Weight (Net / Gross) |
lbs |
35.0 / 38.015.9 / 17.3 |
kg |
CONFORMANCE |
Approvals |
UL / cUL, CE |