Output |
Nominal DC Voltage |
48V |
Current Range |
0 – 5 A |
Rated Power |
240 watts |
Ripple and Noise |
150 mV p-p |
Adjustable Voltage Range |
48 - 53 V |
Voltage Tolerance |
±1% |
Line Regulation |
±0.5% |
Load Regulation |
±1% |
Set-up, Rise Time at full load |
800ms, 40ms/230VAC
800ms, 40ms /115VAC |
Hold-up Time ( typical ) at full load |
24ms/230VAC
24ms/115VAC |
Load De-rating |
De-rating from 40C
60% of full load at 70C |
Output Connectors |
4-pin terminal block ( V+,V-,V+,V- ) |
Input |
Voltage Range |
85 - 264VAC
120 - 370VDC |
Frequency Range |
47 – 63Hz |
Efficiency ( Typical ) |
85% |
AC Current ( Typical ) |
2.8A/115VAC
1.4A/230VAC |
Inrush Current ( Typical ) |
Cold start
27A/115VAC
45A/230VAC |
Leakage Current |
< 3.5mA / 240VAC |
Input Connectors |
3-pin terminal block |
Protection |
Overload Power |
105 - 150% rated output power |
Overload Protection Type |
Constant current limiting, recovers automatically after fault condition is removed |
Over Voltage |
54 – 60V |
Over Voltage Protection Type |
Shut down o/p voltage, re-power on to recover |
Over Temperature |
100 C ±5 % |
Over Temperature Protection Type |
N/A |
Environmental Specifications |
Operating Temperature Ranges |
-10 to 70C ( 14 to 158F ) |
Storage Temperature Range |
-20 to 85C ( -4 to 185F ) |
Operating Humidity Range |
20 - 90% RH non-condensing |
Storage Humidity Range |
10 - 95% RH |
Din Rail Mountable |
Mounts to standard 35 mm DIN rail in accordance with DIN EN 60175 |
MTBF |
289,900 hours based on MIL-HDBK-217F @25 C |
Product Weight and Dimensions |
Weight |
1.12kg, 2.5lbs |
Dimensions |
125.5 x 125.2 x 100mm
4.94 x 4.93 x 3.94 inches |
Packaging |
Shipping Weight |
1.23kg, 2.7lbs |
Shipping Dimensions |
145 x 145 x 125mm, 5.7 x 5.7x 4.9 inches |
Standards and Certifications |
Safety |
UL508, UL60950-1, TUV EN60950-1 |
Emissions |
EN55011,EN55022 (CISPR22)
Class B, EN61000-3-2,-3 |
Mechanical Stability |
Vibration: IEC 60068-2-6
Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes |
EMC and Immunity |
EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A |
Industrial Safety |
UL508 (Safety standard for Industrial Control Equipment ) |
Environmental |
Reach, RoHS and WEEE Compliant |
Other |
ECCN: 5A991 |
HTSUS Number: 8504.40.6012 |