| Environmental Product Compliance |
| REACH SVHC |
Lead 7439-92-1 |
| China RoHS |
Environmentally Friendly Use Period = 25; |
| General |
| Net weight |
1.3 kg |
| Efficiency |
typ. 91.2 % (120 V AC) |
|
typ. 92 % (230 V AC) |
| Insulation voltage input/output |
4 kV AC (type test) |
|
2 kV AC (routine test) |
| Insulation voltage input / PE |
3.5 kV AC (type test) |
|
2.4 kV AC (routine test) |
| Insulation voltage output / PE |
0.5 kV DC (type test) |
|
0.5 kV DC (routine test) |
| Protection class |
I |
| Degree of protection |
IP20 |
| MTBF (IEC 61709, SN 29500) |
> 1196000 h (25 °C) |
|
> 749000 h (40 °C) |
|
> 355000 h (60 °C) |
| Mounting position |
horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions |
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
| Standards and Regulations |
| Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
| Standard - Safety of transformers |
EN 61558-2-16 (air clearances and creepage distances only) |
| Standard - Electrical safety |
IEC 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations |
EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage |
IEC 60950-1 (SELV) |
|
EN 60204-1 (PELV) |
| Standard - Safe isolation |
DIN VDE 0100-410 |
| Standard – Limitation of mains harmonic currents |
EN 61000-3-2 |
| Shipbuilding approval |
DNV GL, PRS, BV, LR, ABS |
| UL approvals |
UL Listed UL 508 |
|
UL/C-UL Recognized UL 60950-1 |
|
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
| Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) |
5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C) |
| Approval - requirement of the semiconductor industry with regard to mains voltage dips |
SEMI F47-0706; EN 61000-4-11 |
| Rail applications |
EN 50121-3-2 |
| Overvoltage category (EN 60950-1) |
II (≤ 5000 m) |
| Overvoltage category (EN 61010-1) |
II (≤ 5000 m) |
| Overvoltage category (EN 62477-1) |
III (≤ 2000 m) |
| Connection data, input |
| Connection method |
Screw connection |
| Conductor cross section solid min. |
0.2 mm² |
| Conductor cross section solid max. |
2.5 mm² |
| Conductor cross section flexible min. |
0.2 mm² |
| Conductor cross section flexible max. |
2.5 mm² |
| Conductor cross section AWG min. |
24 |
| Conductor cross section AWG max. |
14 |
| Stripping length |
6.5 mm |
| Output data |
| Nominal output voltage |
12 V DC |
| Setting range of the output voltage (USet) |
12 V DC ... 15 V DC (constant capacity) |
| Nominal output current (IN) |
15 A |
| Static Boost (IStat.Boost) |
17.5 A |
| Dynamic Boost (IDyn.Boost) |
20 A (5 s) |
| Selective Fuse Breaking (ISFB) |
60 A (15 ms) |
| Derating |
> 60 °C (2.5%/K) |
| Connection in parallel |
Yes, for redundancy and increased capacity |
| Connection in series |
yes |
| Feedback resistance |
≤ 25 V DC |
| Control deviation |
< 0.5 % (Static load change 10 % ... 90 %) |
|
< 4 % (Dynamic load change 10 % ... 90 %, (10 Hz)) |
|
< 0.25 % (change in input voltage ±10 %) |
| Residual ripple |
< 50 mVPP (with nominal values) |
| Output power |
180 W |
| Typical response time |
300 ms (from SLEEP MODE) |
| Maximum power dissipation in no-load condition |
< 4 W (120 V AC) |
|
< 4 W (230 V AC) |
| Power loss nominal load max. |
< 18 W (120 V AC) |
|
< 16 W (230 V AC) |
| Connection data for signaling |
| Connection method |
Push-in connection |
| Conductor cross section solid min. |
0.2 mm² |
| Conductor cross section solid max. |
1.5 mm² |
| Conductor cross section flexible min. |
0.2 mm² |
| Conductor cross section flexible max. |
1.5 mm² |
| Conductor cross section AWG min. |
24 |
| Conductor cross section AWG max. |
16 |
| Stripping length |
8 mm |
| Dimensions |
| Width |
50 mm |
| Height |
130 mm |
| Depth |
125 mm |
| Width with alternative assembly |
122 mm |
| Height with alternative assembly |
130 mm |
| Depth with alternative assembly |
53 mm |
| Weight per piece |
1112.0 GRM |
| Input data |
| Nominal input voltage range |
100 V AC ... 240 V AC |
|
110 V DC ... 250 V DC |
| Input voltage range |
100 V AC ... 240 V AC -15 % ... +10 % |
|
110 V DC ... 250 V DC -18 % ... +40 % |
| Dielectric strength maximum |
300 V AC 60 s |
| AC frequency range |
50 Hz ... 60 Hz -10 % ... +10 % |
| Discharge current to PE |
< 3.5 mA |
| Current consumption |
2.4 A (100 V AC) |
|
120 V AC |
|
230 V AC |
|
1.1 A (240 V AC) |
| Nominal power consumption |
221 VA |
| Inrush surge current |
typ. 15 A (at 25 °C) |
| Mains buffering |
typ. 55 ms (120 V AC) |
|
typ. 56 ms (230 V AC) |
| Input fuse |
8 A (slow-blow, internal) |
| Choice of suitable circuit breakers |
10 A ... 16 A (Characteristic B, C, D, K or comparable) |
| Type of protection |
Transient surge protection |
| Protective circuit/component |
Varistor, gas-filled surge arrester |
| Connection data, onput |
| Connection method |
Screw connection |
| Conductor cross section solid min. |
0.2 mm² |
| Conductor cross section solid max. |
6 mm² |
| Conductor cross section flexible min. |
0.2 mm² |
| Conductor cross section flexible max. |
4 mm² |
| Conductor cross section AWG min. |
24 |
| Conductor cross section AWG max. |
14 |
| Stripping length |
6.5 mm |
| Ambient conditions |
| Degree of protection |
IP20 |
| Ambient temperature (operation) |
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) |
-40 °C |
| Ambient temperature (storage/transport) |
-40 °C ... 85 °C |
| Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
| Climatic class |
3K3 (in acc. with EN 60721) |
| Degree of pollution |
2 |
| Installation height |
≤ 5000 m (> 2000 m, observe derating) |
| Approvals |
| |
- cULus Listed
- cULus Recognized
- UL Recognized
- cUL Recognized
- cUL Listed
- UL Listed
|