  • High Power and rugged design
  • Short Circuit, Over-Voltage, Over-current Protection
  • 90-264VAC Auto Ranging Input
  • 47~56VDC Adjustable Output
  • -40C to +70C Operating Temperature
  • Supports Parallel Operation
  • Dry Contact DC Alarm

 

Mfg SKU # : PSDIN-48-120W
Our Price : $84.95
Stock : 115
Quantity :
The PSDIN-48-120W of PSDIN Series of Industrial DIN Rail mount high efficiency switching power supplies operate over a wide temperature range of -40C to +70C. This model is 120W. The input is 90 to 264VAC auto-ranging with wire terminal connections. The output is 48VDC nominal with an adjustment range from 47VDC to 56VDC. There is a switch for single or parallel operation. There is an alarm output to provide a dry contact closure to trigger an alarm if the DC output fails, like during a grid power failure. The relay is closed when DC output is normal and open when DC output is in fault condition due to overload or safety shutdown.

Input Operating Range

90-264VAC ; 47-63Hz

Input In-rush Current

35A Max

Input Current

2.2A @ 115VAC ; 1.10A @ 230VAC

Output Voltage

47~ 56VDC (adjustable)

Cont. Load Current

2.5A

Maximum Output Power

120W

Peak Power (10sec @ 220VAC)

180W

Line Regulation

+/- 0.5%

Load Regulation

+/- 1%

Voltage Overshoot

<5%

Ripple / Noise

100mV Peak

Ripple / Noise

100mV Peak

Efficiency

90% Minimum

Dielectric Strength

1500V rms , 1 min, 10mA Max

Insulation Resistance

10M Ohms

Protection

Short Circuit, Over-Voltage, Over-Current, Over Power

Alarm Output (“DC” and “OK”)

1A @ 30VDC, 0.5A @ 125VAC. DC OK = Closed, DC Fault = Open

Safety Standards

GB4943 / EN60950-1

EMI Standards

FCC PART 15 CLASS B, EN55022, EN55024

Harmonic Current

EN61000-3-2 Class D

EMS

EN61000-4-x Level 3&4

Operating Temp

-40°C to 70°C (-40°F to 158°F)

Operating Humidity

5% to 95% non- condensing

Storage Temp

-40°C to 85°C (-40°F to 185°F)

MTBF

200,000 hrs

Altitude

2000m (6562ft)

Vibration

10-500Hz 2G 10min Sweep, 20G Surge 11ms

Case Size

135 x 121 x 40mm (5.3 x 4.8 x 1.6”)

Weight

0.59 Kg (1.3 Lb)