M-7017 - 8 Channel Voltage Input & Current Input, Analog Input Data Acquisition Module. Communicable over Modbus RTU and RS-485 by ICP DAS
|
|
|
8 Channel Voltage Input & Current Input, Analog Input Data Acquisition
Module. Communicable over Modbus RTU and RS-485. Supports operating temperatures
between -25 to 75°C. Input types include ±150mV, ±500mV , ±1V, ±5V, ±10V and
±20mA.
|
|
|
The M-7017 is an 8-channel voltage and current input module. The M-7000
series is a family of network data acquisition and control modules that support
Modbus RTU. They can be remotely controlled using a set of commands called DCON
protocol. With the Modbus RTU protocol, it can easily communicate with most
popular SCADA/HMI software and PLCs.
- Indication LED Light
- For power and communication
- Over voltage protection: 240Vrms
- Supports Modbus and DCON Protocol
- Din Rail Mount
- Analog Input Channels: 8 differential
Analog Input |
Input Channels |
8 differential |
Input Type |
±150mV, ±500mV , ±1V, ±5V, ±10V
±20mA (requires optional external 125 ohm resistor) |
Resolution |
16-bit |
Sampling Rate |
10 Samples/ Second |
Accuracy |
±0.1% |
BandWidth |
15.7 Hz |
Zero drift |
±20uV/°C |
Span drift |
±25ppm/°C |
Input Impedance |
20M Ohms |
Common Mode Rejection |
86dB min |
Normal Mode Rejection |
100dB |
Over voltage Protection |
±35V(P-P) |
Intra-module Isolation, Field to Logic |
3000 VDC |
Interface |
Interface |
RS-485 |
Format |
N, 8, 1 |
Baud Rate |
1200 ~ 115200bps |
LED Display |
1
LED |
As Power / Communication Indicator |
1 LED |
Power |
Input |
+10 to +30VDC |
Power Consumption |
1.3W |
Protocol |
Support Modbus and DCON Protocol |
Yes |
Watchdog |
Yes, Module, Communication (Programmable over DCON) firmware version
B300 and later |
Environment |
Operating temperature |
-25 to 75°C |
Storage temperature |
-40 to 85°C |
Humidity |