ICP DAS M-7052 - 8 Channel Isolated Digital Input Counter Data Acquisition Module, communicable over Modbus RTU and RS-485 by ICP DAS
|
|
|
|
8 Channel Isolated Digital Input Counter Data Acquisition Module,
communicable over Modbus RTU and RS-485, supports operating temperatures from
-25 to 75°C
|
|
|
The M-7052 device is a data acquisition and control modules that support
Modbus RTU. They can be remotely controlled using a set of commands called DCON
protocol. With the Modbus RTU protocol, it can easily communicate with most
popular SCADA/ HMI software and PLCs.
- Communicartion Interface: RS-485
- Digital Input Channels: 8
- 6 fully independent channels
- 2 common ground channels
- D/I can be used as counter
- Din Rail Mount
|
Communication |
|
Interface |
RS-485 |
|
Bias Resistor |
No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4
or SG-785.) |
|
Format |
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
|
Baud Rate |
1200 to 115200 bps |
|
Logic level 1: +3.5 to 30V |
|
Protocol |
Modbus RTU, DCON |
|
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
|
LED Indicators/Display |
|
System LED Indicator |
Yes, 1 as Power/Communication Indicator |
|
I/O LED Indicators |
Yes, 8 LEDs as Digital Input Indicators |
|
7-Segment LED Display |
- |
|
Isolation |
|
Intra-module Isolation, Field-to-Logic |
5000 Vrms |
|
EMS Protection |
|
ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal |
|
±8 kV Air for Random Point |
|
EFT (IEC 61000-4-4) |
±2 kV for Power Line |
|
Surge (IEC 61000-4-5) |
- |
|
Power |
|
Reverse Polarity Protection |
Yes |
|
Input Range |
10 ~ 30 VDC |
|
Consumption |
0.2 W |
|
Mechanical |
|
Dimensions (L x W x H) |
123 mm x 72 mm x 35 mm |
|
Installation |
DIN-Rail or Wall Mounting |
|
Environment |
|
Operating Temperature |
-25°C ~ +75°C (-13°F ~ +167°F) |
|
Storage Temperature |
-40°C ~ +85°C (-40°F ~ +185°F) |
|
Humidity |
10 ~ 95% RH, Non-condensing |
I/O Specifications
|
Digital Input/Counter |
|
Channels |
8 |
|
Type |
Dry Contact |
- |
|
Wet Dry |
Sink/Source |
|
Wet Contact |
On Voltage Level |
+4 ~ 30 VDC |
|
Off Voltage Level |
+1 VDC Max. |
|
Dry Contact |
On Voltage Level |
- |
|
Off Voltage Level |
- |
|
Effective Distance for Dry Contact |
- |
|
Counters |
Max. Count |
65535 (16-bit) |
|
Max. Input |
100 hz |
|
Min. Pulse Width |
5 ms |
|
Input Impedence |
3 KΩ |
|
Chanell-to-Channel Isolation |
- |
|
Overvoltage Protection |
±35 VDC |
|
|
|
|