Voltage & Current Thermocouple Input Data Acquisition Module with 1 AI, 1 DI, 2 DO Channels, and FREE EZ Data Logger Software communicable over RS-485. Supports operating temperatures between -25 to 75°C.
|
|
|
The I-7011 module provides cost-effective protection and conditioning for a wide range of valuable industrial control signals and systems. DCON utility can help users to configure and test I-7011 modules. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals. I-7011 comes with FREE EZ Data Logger Software.

| Analog Input |
| Input Channels |
1 |
| Input Type |
+/-15mV, +/-50mV, +/-100mV,+/- 500mV , +/-1V,+/- 2.5V
+/- 20mA (requires optional external 125 ohm resistor)
Thermocouple( Type J, K, T, E, R, S, B, N, C) |
| Resolution |
16-bit |
| Sampling Rate |
10 Samples/ Second |
| Accuracy |
+/-0.05% |
| Zero Drift |
+/-0.5uV/°C |
| Span Drift |
25ppm/°C |
| Band Width |
5.24Hz |
| Common Mode Rejection |
150dB |
| Normal Mode Rejection |
100dB |
| Input Impedance |
20M Ohms |
| Intra-module Isolation, Field to Logic |
3000 VDC |
| Digital Input |
| Channels |
1 |
| Logic Level 0 |
+1V max |
| Logic Level 1 |
+3.5V to 30V |
| Max Input Frequency |
50Hz |
| Min. Pulse Width |
1 ms |
| Digital Output |
| Channels |
2 |
| Output Type |
Sink, Open Collector to 30V |
| Output Load |
30mA max. per channel |
| Power dissipation |
300 mW |
| Interface |
| Interface |
RS-485 |
| Format |
N, 8, 1 |
| Baudrate |
1200 ~ 115200 bps |
| LED Display |
| 1 LED as Power/ Communication indicator |
| 4 1/2 digits (for I-7011D) |
| Power |
| Input |
+10 to +30 Vdc |
| Power Consumption |
0.9 W (I-7011) / 1.5W(I-7011D) |
| Environment |
| Operating temperature |
-25°C to 75 °C |
| Storage temperature |
-30°C to 75 °C |
| Humidity |
5 to 95%, non-condensing |
| Thermocouple Type |
Range (°C) |
| C |
0 ~ 2320 |
|
|
|
|