ICF-1171I-S-ST-T - Industrial CAN to Fiber Optic Converter for Distance Extension, ST Single-mode, -40 to 75 by MOXA
|
|
|
ICF-1171I-S-ST-T_SUMMARY.html
- Transmits data for up to 40 km over optical fiber
- Converts CAN signals to fiber and vice versa
- Supports CAN 2.0A, CAN 2.0B, and CAN FD; conforms with the ISO 11898 standard
- CAN 2.0 supports auto-baudrate
- CAN 2.0 arbitration rate up to 1 Mbps
- CAN FD arbitration rate up to 1 Mbps; data rate up to 5 Mbps
- Dual power inputs for redundancy
- Wide-temperature model available for -40 to 75C environments
- DIP switch for 120-ohm terminal resistance
- Rotary switches for CAN 2.0-CAN FD arbitration and data rate configuration
- LEDs for CAN bus diagnostics, fiber diagnostics, and power input status
|
|
|
ICF-1171I-S-ST-T_DESCRIPTION.html
The ICF-1171I Series CAN-to-fiber converters are used in pairs to
connect two CAN 2.0 or two CAN FD devices or networks via single-mode
or multi-mode optical fiber. The ICF-1171I provides 2-kV isolation
protection for the CAN interface and dual power inputs to ensure that
your CANbus system will work uninterrupted.
ICF-1171I-S-ST-T.html
Serial Interface
-
Optical Fiber
- 100Base-Fx ports (single-mode-multi-mode ST connector)
-
Optical Fiber
- Note: The typical distance of a specific fiber transceiver can be computer using Link budget (dB) > Dispersion penalty (dB) + Total link loss (dB).
CAN Interface
-
Isolation
-
No. of Ports
-
Signals
- CAN_L, CAN_H, CAN Signal GND
-
Terminator
-
Protocols
- CAN 2.0A, CAN 2.0B, CAN FD, compatible with ISO 11898 standard (DIP switch to select CAN 2.0-CAN FD setting)
Fiber Interface
-
No. of Ports
-
Connector
-
Optical Fiber
- Single-mode, typical distance 40 km
Multi-mode, typical distance 2 km
Power Parameters
-
Input Current
-
Input Voltage
-
No. of Power Inputs
-
Power Connector
Relays
-
Contact Current Rating
- Resistive load: 1 A @ 30 VDC
-
Pinouts
Physical Characteristics
-
Housing
-
IP Rating
-
Dimensions
- 30.3 x 70 x 115 mm (1.19 x 2.76 x 4.53 in)
-
Weight
-
Installation
- DIN-rail mounting, Wall mounting (with optional kit)
Environmental Limits
-
Operating Temperature
-
Storage Temperature (package included)
-
Ambient Relative Humidity
- 5 to 95% (non-condensing)
Standards and Certifications
-
EMC
-
EMI
- CISPR 32, FCC Part 15B Class A
-
EMS
- IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V-m IEC 61000-4-4 EFT: Power: 4 kV; Signal: 2 kV IEC 61000-4-5 Surge: Power: 2 kV, Signal: 2 kV IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V-m; Signal: 10 V-m IEC 61000-4-8 PFMF
-
International Approval
-
Safety
-
Vibration
MTBF
Warranty
|
|