Need assistance or guidance?

Contact us @: 1-800-301-9097
Login / Register Contact Us
 
M-7011D - 1-channel Analog Input, 1-channel Digital Input, and 2-channel Digital Output data acquisition module with display by ICP DAS

M-7011D - 1-channel Analog Input, 1-channel Digital Input, and 2-channel Digital Output data acquisition module with display
by ICP DAS

Write a review Write a review

1-channel Analog Input, 1-channel Digital Input, and 2-channel Digital Output data acquisition module with display. Supports Thermocouple Input, Voltage Input and Current Input. Communicable over Modbus RTU and RS-485. Supports operating temperatures between -25 to 75°C (-13F ~ 167F).

Mfg SKU # : M-7011D
List Price : $399.00
Our Price : $392.00
Stock : 2
Quantity :

The M-7011D data acquisition Remote I/O module is a thermocouple input, voltage and current input module. It comes with a LED display, which works as Power/ Communication indicator. It provides cost-effective protection and conditioning for a wide range of valuable industrial control signals and systems. We provide free DCON utility which can help users to configure and test M-7011 modules. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals.

Analog Input
Input Channels 1
Input Type ±15mV, ±50mV, ±100mV,± 500mV , ±1V,± 2.5V
± 20mA (requires optional external 125 ohm resistor)
Thermocouple( Type J, K, T, E, R, S, B, N, C)
Resolution 16-bit
Sampling Rate 10 Samples/ Second
Accuracy ±0.05%
Zero Drift ±0.5uV/°C
Span Drift 25ppm/°C
Band Width 5.24Hz
Common Mode Rejection 150dB
Normal Mode Rejection 100dB
Input Impedance 20M Ohms
Intra-module Isolation, Field to Logic 3000 VDC
Digital Input
Channels 1
Logic Level 0 +1V max
Logic Level 1 +3.5V to 30V
Max Input Frequency 50Hz
Min. Pulse Width 1 ms
Digital Output
Channels 2
Output Type Sink, Open Collector to 30V
Output Load 30mA max. per channel
Power dissipation 300 mW
Interface
Interface RS-485, Modbus RTU
Format N, 8, 1
Baudrate 1200 ~ 115200 bps
LED Display
1 LED as Power/ Communication indicator
4 1/2 digits for I-7011D
Power
Input +10 to +30 Vdc
Power Consumption 0.9 W (I-7011) / 1.5W(I-7011D)
Protocol
Support Modbus and DCON Protocol Yes
Watchdog Yes, Module, Communication (Programmable)
Environment
Operating temperature -25°C to 75 °C
Storage temperature -30°C to 75 °C
Humidity 5 to 95%, non-condensing
Thermocouple Type Range (°C)
J -210 ~ +760
K -270 ~ +1372
T -270 ~ +400
E -270 ~ +1000
R 0 ~ +1768
S 0 ~ +1768
B 0 ~ +1820
N -270 ~ 1300
C 0 ~ 2320

Copyright © 2024 iComTech. All rights reserved. Shopping Cart Software powered by ecMidas.