ICP DAS M-7018 - 8 Channel Analog Input Data Acquisition Module communicable over Modbus RTU and RS-485 by ICP DAS
|
|
|
|
8 Channel Analog Input Data Acquisition Module. Supports Current Input Types
of +/-20mA (requires optional external 125 ohm resistor), Voltage Input Types:
+/-15mV, +/-50mV, +/-100mV, +/-500mV, +/-1V, +/-2.5V and Thermocouple Input
Types J, K, T, E, R, S, B, N, and C. Communicable over Modbus RTU and RS-485.
Supports operating temperatures between -25 to 75°C (-13F ~ 167F).
|
|
|
The M-7000 series is a family of network data acquisition and control modules
that support Modbus RTU. They can be remotely controlled using a set of commands
called DCON protocol. With the Modbus RTU protocol, it can easily communicate
with most popular SCADA/ HMI software and PLCs.
- Indication LED Light
- For power and communication
- Over voltage protection:240Vrms
- Support Modbus and DCON Protocol
- Analog Input Channels: 8 differential
- Type: mV, V , mA
- Thermocouple: Type J, K, T, E, R, S, B, N, C
- Din Rail Mount
|
Analog Input |
|
Input Channels |
8 differential |
|
Input Type |
+/-15mV, +/-50mV, +/-100mV, +/-500mV, +/-1V, +/-2.5V
+/-20mA (requires optional external 125 ohm resistor)
Thermocouple Type J, K, T, E, R, S, B, N, C |
|
Resolution |
16-bit |
|
Sampling Rate |
10 Samples/ Second |
|
Accuracy |
+/-0.1% |
|
Band Width |
15.7 Hz |
|
Zero Drift |
0.5uV/°C |
|
Span Drift |
25ppm/°C |
|
Input Impedance |
20M Ohms |
|
Common Mode Rejection |
150dB |
|
Normal Mode Rejection |
100dB |
|
Over Voltage Protection |
+/-35V |
|
Open Thermocouple Detection |
No |
|
Intra-module Isolation, Field to Logic |
3000 VDC |
|
Interface |
|
Interface |
RS-485 |
|
Format |
N, 8, 1 |
|
Baud Rate |
1200 ~ 115200bps |
|
LED Display |
|
1 LED as Power/ Communication indicator |
|
Power |
|
Input |
+10 to +30 Vdc |
|
Power Consumption |
1.0W |
|
Protocol |
|
Support Modbus and DCON Protocol |
Yes |
|
Environment |
|
Operating temperature |
-25 to 75°C |
|
Storage temperature |
-40 to 85°C |
|
Humidity |
5 to 95% RH, non-condensing |
Note: We recommend to choose M-7108Z for
accurate thermocouple measurement.
Thermocouple Type
|
Type |
Range (°C) |
|
J |
-210 ~ +760 |
|
K |
-270 ~ +1372 |
|
T |
-270 ~ +400 |
|
E |
-270 ~ +1000 |
|
R |
0 ~ +1768 |
|
S |
0 ~ +1768 |
|
B |
0 ~ +1820 |
|
N |
-270 ~ 1300 |
|
C |
0 ~ 2320 |
|
|
|
|