M-7052D - 8-channel Isolated Digital Input Counter Data Acquisition Module with Display, supports Modbus RTU and RS-485 by ICP DAS
|
|
|
8 Channel Isolated Digital Input Counter Data Acquisition Module,
communicable over Modbus RTU and RS-485 with Display, supports operating
temperatures from -25 to 75°C
|
|
|
The M-7052D device is a network data acquisition and control modules that
support Modbus RTU. They can be remotely controlled using a set of commands
called DCON protocol. With the Modbus RTU protocol, it can easily communicate
with most popular SCADA/ HMI software and PLCs.
- Communicartion Interface: RS-485
- Digital Input Channels: 8
- 6 fully independent channels
- 2 common ground channels
- D/I can be used as counter
- Din Rail Mount
Communication |
Interface |
RS-485 |
Bias Resistor |
No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4
or SG-785.) |
Format |
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
Baud Rate |
1200 to 115200 bps |
Logic level 1: +3.5 to 30V |
Protocol |
Modbus RTU, DCON |
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicators/Display |
System LED Indicator |
Yes, 1 as Power/Communication Indicator |
I/O LED Indicators |
Yes, 8 LEDs as Digital Input Indicators |
7-Segment LED Display |
- |
Isolation |
Intra-module Isolation, Field-to-Logic |
5000 Vrms |
EMS Protection |
ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal |
±8 kV Air for Random Point |
EFT (IEC 61000-4-4) |
±2 kV for Power Line |
Surge (IEC 61000-4-5) |
- |
Power |
Reverse Polarity Protection |
Yes |
Input Range |
10 ~ 30 VDC |
Consumption |
0.6 W |
Mechanical |
Dimensions (L x W x H) |
123 mm x 72 mm x 35 mm |
Installation |
DIN-Rail or Wall Mounting |
Environment |
Operating Temperature |
-25°C ~ +75°C (-13°F ~ +167°F) |
Storage Temperature |
-40°C ~ +85°C (-40°F ~ +185°F) |
Humidity |
10 ~ 95% RH, Non-condensing |
I/O Specifications
Digital Input/Counter |
Channels |
8 |
Type |
Dry Contact |
- |
Wet Dry |
Sink/Source |
Wet Contact |
On Voltage Level |
+4 ~ 30 VDC |
Off Voltage Level |
+1 VDC Max. |
Dry Contact |
On Voltage Level |
- |
Off Voltage Level |
- |
Effective Distance for Dry Contact |
- |
Counters |
Max. Count |
65535 (16-bit) |
Max. Input |
100 hz |
Min. Pulse Width |
5 ms |
Input Impedence |
3 KΩ |
Chanell-to-Channel Isolation |
- |
Overvoltage Protection |
±35 VDC |
|
|