ICP DAS M-7058 - 8 Channel Isolated AC Voltage Digital Input Data Acquisition Module with 80 ~ 250VAC inputs. Communicable via M by ICP DAS
|
|
|
|
8 Channel Isolated AC Voltage Digital Input Data Acquisition Module with 80 ~
250VAC inputs. Communicable via ModBus RTU and RS-485, supports operating
temperatures from -25 to 75°C
|
|
|
M-7058 is intelligently designed to provide signal conditioning system
monitoring and safe value settings. M-7058 is a cost-effective solution for a
wide range of valuable industrial control signals and systems. The DCON utility
can help users to configure and test M-7058 (Isolated digital Input module w/Modbus).
Plenty of library functions and demo programs are provided to let users develop
programs easily under Windows, Linux and DOS operating systems. The
communication interface is modbus protocol via RS-485. Users may mount the
modules on a DIN rail, panel or wall. Modules have a screw-terminal block to
connect to the signals.
|
Digital Input |
|
Channels |
8 |
|
Input Type |
AC, Differential, isolated |
|
Off Voltage Level |
30VAC max. |
|
On Voltage Level |
80 ~ 250VAC |
|
AC Frequency |
50~60Hz ( > 45Hz Min.) |
|
Input Impedance |
68K Ohm, 1W |
|
Counters |
channels : 8 |
|
Max. Counters : 16-bit (65535) |
|
Max. Input Frequency : 100Hz |
|
Min. Pulse Width : 5ms |
|
Photo-Isolation |
5000Vrms |
|
Interface |
|
Interface |
Modbus RTU |
|
Format |
N, 8, 1 |
|
Baud Rate |
1200 ~ 115200bps |
|
LED Display |
1 LED as Power/ Communication indicator
8 LEDs as Digital Input indicators (for i-7058D) |
|
Power |
|
Input Voltage Range |
10~30VDC |
|
Power Consumption |
0.3W (i-7058) / 1.0W (i-7058D) |
|
Environment |
|
Operating Temperature |
-25 to 75°C |
|
Storage Temperature |
-40 to 85°C |
|
Humidity |
5 to 95%, non-condensing |
|
|
|
|