tM-P8 - 8-channel Isolation Digital Input Module by ICP DAS
|
|
|
8-channel Isolated Digital Input Module, communicable over RS-485 and Modbus RTU, supports operating temperatures from -25 °C ~ +75 °C
|
|
|
The tM-P8 offers 8 channels for digital input, each of which features photocouple isolation. In addition input can be either sink- or source-type using wire connections and all channels can be used as 16-bit counters. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided.
- Sink- and Source-type Digital Inputs
- Photocouple Isolation
- All Channels Can Be Used As 16-bit Counters
- Dual Watchdog
- Cost-effective
- Wide Operating Temperature Range: -25 °C ~ +75 °C
I/O Specifications
Digital Input/Counter |
Input Channels |
8 |
Type |
Wet Contact (Sink, Source) |
On Voltage Level |
+3.5 VDC ~ 50 VDC |
Off Voltage Level |
+1 VDC Max. |
Input Impedance |
10 KΩ, 0.66 W |
Counters |
Channels |
8 |
Max. Count |
65535 (16-bit) |
Max. Input Frequency |
100 Hz |
Min. Pulse Width |
5 ms |
Overvoltage Protection |
70 VDC |
System Specifications
Communication |
Interface |
RS-485 |
Format |
(N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) |
Baud Rate |
1200 ~ 115200 bps |
Protocol |
DCON, Modbus/RTU, Modbus/ASCII |
Dual Watchdog |
Yes, Module (2.3 seconds), Communication (Programmable) |
LED Indicators |
Power |
1 LED as Power Indicator |
Isolation |
Intra-module Isolation,Field-to-Logic |
3750 VDC |
EMS Protection |
ESD (IEC 61000-4-2) |
±4 kV Contact for Each Terminal |
±8 kV Air for Random Point |
EFT (IEC 61000-4-4) |
±4 kV for Power |
Power Requirements |
Reverse Polarity Protection |
Yes |
Powered from Terminal Block |
Yes, 10 ~ 30 VDC |
Consumption |
0.4 W Max. |
Mechanical |
Dimensions (W x L x H) |
52 mm x 98 mm x 27 mm |
Installation |
DIN-Rail Mounting |
Environment |
Operating Temperature |
-25 °C ~ +75 °C |
Storage Temperature |
-30 °C ~ +75 °C |
Humidity |
10 ~ 95% RH, Non-condensing |
|
|